Refrigeration第 60 / 110 题
On a system with a condensing saturation temperature of 105 F and a liquid line temperature of 95 F, what is the subcooling?
a.5 degrees
b.8 degrees
c.10 degrees
d.15 degrees
解析
Subcooling equals the saturation temperature minus the liquid line temperature: 105 F minus 95 F equals 10 degrees. This is a typical target range for many TXV systems. Low subcooling can indicate an undercharge, while high subcooling can indicate an overcharge or restriction.
免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- Superheat is defined as the temperature of the refrigerant vapor above what?
- A technician measures a suction pressure whose saturation temperature is 40 F and a suction line temperature of 52 F. What is the superheat?
- Subcooling is measured at which point in the system?
- On a fixed-orifice (piston) system, which method is generally used to check the charge?
- Under EPA Section 608, what must a technician do with refrigerant before opening most systems for service?
- EPA Section 608 certification is required for technicians who do what?