第 5 章,共 6 章~15% 占考试比重

Type III: Low-Pressure Appliances

Type III certification covers low-pressure appliances, the large centrifugal chillers that use refrigerants like R-11, R-123, and R-1233zd. Because these machines run in a vacuum, they demand special recovery levels, careful pressurization limits, and equipment such as purge units. This chapter walks through the facts unique to low-pressure work.

Low-Pressure Appliances Defined

A low-pressure appliance uses a refrigerant with a boiling point above roughly 50°F at atmospheric pressure, so the machine operates at or below atmospheric pressure — in other words, in a partial vacuum on the low side. Classic low-pressure refrigerants are CFC-11, HCFC-123, and the newer low-GWP HFO R-1233zd, all used in large centrifugal chillers that cool commercial buildings. Because the evaporator runs in a vacuum, any leak draws air and moisture inward rather than pushing refrigerant out, which shapes almost every Type III procedure. Servicing these chillers is specialized, high-value work, and the recovery, pressurization, and purge rules below apply specifically to low-pressure machines.

Low-pressure refrigerants boil above about 50°F
The chiller operates at or below atmospheric pressure, so its low side sits in a vacuum.
40 CFR §82.152
R-11, R-123, and R-1233zd are typical low-pressure refrigerants
These are used in large centrifugal chillers for commercial building cooling.
Leaks pull air and moisture inward
Because the low side is under vacuum, a leak admits air and water rather than releasing refrigerant.

Recovery from Low-Pressure Systems

The required recovery level for a low-pressure appliance is 25 mm Hg absolute, and this figure is the same whether your recovery equipment was made before or after November 15, 1993. Note the units: 25 millimeters of mercury absolute is a deep vacuum, roughly 29 inches of mercury vacuum on a compound gauge, far deeper than the levels used for high-pressure systems. Because low-pressure refrigerant boils near room temperature, recovery is helped by keeping the refrigerant warm and the recovery cylinder cool so vapor migrates toward the cylinder. You may circulate warm water through the chiller tubes or use the machine's own heaters to raise the refrigerant temperature and speed recovery, but never apply a torch. Recover liquid first, then draw the remaining vapor down to 25 mm Hg absolute.

Recover low-pressure appliances to 25 mm Hg absolute
This deep-vacuum level applies regardless of when the recovery equipment was manufactured.
40 CFR §82.156
Keep refrigerant warm and the cylinder cool
Warming the chiller and cooling the recovery cylinder drives vapor toward the cylinder and speeds recovery.
Warm the chiller with water, never a torch
Circulating warm water or using built-in heaters raises refrigerant temperature safely; an open flame is dangerous.

Pressurization and Leak Testing

Because a low-pressure chiller normally runs in a vacuum, you must add pressure to test for leaks, and doing this safely is critical. Never pressurize a low-pressure appliance above 10 psig. Low-pressure chillers are protected by a rupture disk that is typically set to relieve at 15 psig, so exceeding 10 psig risks bursting the disk and venting the charge. To raise pressure for a leak test you may add a small amount of refrigerant vapor and then nitrogen, or use controlled heat, but you must watch the gauge closely and stay under the limit. Some technicians pressurize just enough to bring the refrigerant above atmospheric so an electronic detector or bubble test can find the leak. Never use oxygen or compressed air, and never let the pressure approach the rupture-disk setting.

Never exceed 10 psig in a low-pressure appliance
Pressurizing above 10 psig risks bursting the rupture disk and releasing the charge.
40 CFR §82.156
The rupture disk typically relieves at 15 psig
This safety device protects the low-pressure shell, so keep test pressure well below its setting.
Use refrigerant and nitrogen, never oxygen
Add a trace of refrigerant with nitrogen for leak testing; oxygen or compressed air can cause an explosion.

Purge Units and Non-Condensables

Because a low-pressure chiller runs under vacuum, air and moisture leak inward and collect as non-condensable gas at the top of the condenser, where they raise head pressure and cut efficiency. A purge unit removes these non-condensables from the high point of the system and vents them, ideally recovering refrigerant vapor that would otherwise escape with the purged air. High-efficiency purge units greatly reduce refrigerant loss compared with old designs, releasing very little refrigerant per pound of air purged. Frequent purging is a warning sign that the machine has a leak drawing air in, so a rising purge rate should prompt leak repair rather than just more purging. Keeping the purge unit maintained protects both the charge and the chiller's cooling capacity.

A purge unit removes non-condensables from the condenser
Air and moisture collect at the high point and raise head pressure, so the purge unit vents them off.
High-efficiency purge units cut refrigerant loss
Modern purge designs release far less refrigerant per pound of air than older units.
Frequent purging signals an air leak
A rising purge rate means the vacuum side is drawing in air, so find and fix the leak.

Water, Rupture Disks, and Chiller Service

Water is a special hazard in low-pressure chillers because a tube leak lets cooling water enter the refrigerant side while the machine is under vacuum. Water causes corrosion and acid formation, can freeze and damage tubes, and contaminates the refrigerant. If the low-pressure limit control or a high-pressure limit device trips, investigate rather than simply resetting it, because it may be signaling water intrusion or non-condensables. The rupture disk must be kept in good condition and never bypassed. When servicing, isolate and recover the charge before opening the machine, protect the rupture disk from over-pressure, and check the purge and float systems. Handling the large low-pressure recovery cylinders carefully and evacuating to 25 mm Hg absolute round out safe, code-compliant chiller service.

Water intrusion corrodes and contaminates the chiller
A tube leak under vacuum lets water in, causing acid, freezing damage, and refrigerant contamination.
Investigate tripped limit devices, do not just reset
A high- or low-pressure limit trip can signal water or non-condensables that need attention.
Never bypass the rupture disk
The rupture disk protects the low-pressure shell and must be kept sound and unobstructed.
测试你的知识
练习 Type III: Low-Pressure Appliances 的相关题目
立即练习 →

Last updated: July 2026

反馈