Code Admin & Safety第 100 / 110 题
Equipment rated at what current or more requires two entrances to and egress from the working space when the space is large or contains overcurrent devices?
a.800 A
b.600 A
c.1000 A
d.1200 A
解析
For equipment rated 1,200 A or more and over 6 ft wide, two entrances/egress paths to the working space are required.
法律依据: 2023 NEC 110.26(C)(2)免费刷完整 110 道题库 — 无需注册。