Services & Distribution第 34 / 110 题

A branch circuit is protected by a 100-A overcurrent device. What is the minimum copper equipment grounding conductor?

a.#10 AWG
b.#8 AWG
c.#6 AWG
d.#4 AWG

解析

The equipment grounding conductor table requires #8 Cu for an overcurrent device rating up to 100 A.

法律依据: 2023 NEC Table 250.122

免费刷完整 110 道题库 — 无需注册。

同考点相关题目

最近核对: · 审核流程

PrepPass 编辑团队 · 依据官方资料核对 Master Electrician Licensing Exam (NEC-based) · 我们如何核对