Services & Distribution第 44 / 110 题
Two paralleled sets of 500-kcmil Cu (75 C, 380 A each) supply one feeder. What is the combined ampacity before adjustment?
a.500 A
b.620 A
c.380 A
d.760 A
解析
Paralleled conductor ampacities add: 380 A x 2 = 760 A total for the feeder.
法律依据: 2023 NEC Table 310.16免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- Absent a specific exception, what is the maximum overcurrent protection for a #10 Cu conductor?
- A conductor has an allowable ampacity of 115 A, which is not a standard rating. Under the next-standard-size rule (600 A or less), what is the largest permitted overcurrent device?
- What is the smallest conductor size generally permitted to be installed in parallel?
- What is the minimum service disconnecting-means rating for a one-family dwelling?
- What is the minimum vertical clearance of an overhead service drop (not over 300 V) above a residential driveway or sidewalk area limited to pedestrians?
- At a separately derived system such as a transformer, what conductor connects the grounded conductor to the system grounding electrode?