A wet-niche underwater luminaire operating without GFCI protection is limited to a maximum of:
a.120 V
b.24 V
c.15 V
d.30 V
解析
Underwater luminaires must be GFCI protected unless they operate at not more than the low-voltage contact limit of 15 V.
法律依据: 2023 NEC 680.23(A)免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- What is the minimum number of receptacles required at a critical care (Category 1) patient bed location?
- The equipotential bonding grid around a permanently installed pool must use a solid copper conductor no smaller than:
- A required convenience receptacle for a dwelling pool must be located not less than what distance from the inside pool wall?
- A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?
- A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?
- A hermetic compressor has a rated-load current of 24 A. What is the maximum branch-circuit short-circuit and ground-fault device at 175% (next standard size)?