Advanced Wiring第 67 / 110 题

Which nameplate value on an air-conditioning unit is used to size the branch-circuit conductors?

a.Maximum overcurrent protection
b.Nameplate horsepower
c.Minimum circuit ampacity
d.Rated-load amps only

解析

Conductors are sized to the marked minimum circuit ampacity (MCA); the maximum overcurrent protective device (MOCP) sizes the breaker or fuse.

法律依据: 2023 NEC 440.4