What is the real power of a three-phase load at 480 V, 50 A, and 0.85 power factor?
a.24,960 W
b.41,568 W
c.30,000 W
d.35,326 W
解析
P = 1.732 x V x I x PF = 1.732 x 480 x 50 x 0.85 = 35,326 W.
免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A load draws 80 kW of real power and 100 kVA of apparent power. What is the power factor?
- For a load of 80 kW real and 100 kVA apparent, what is the reactive power?
- In a balanced wye (star) three-phase system, the line current is:
- In a balanced delta three-phase system, the line current equals:
- In a 208Y/120-V wye system, what is the phase (line-to-neutral) voltage?
- In a 480Y/277-V system, what is the line-to-neutral voltage?