Theory & Design第 93 / 110 题

A continuous load draws 40 A. At what minimum ampacity must the branch-circuit conductors and overcurrent device be rated?

a.50 A
b.40 A
c.32 A
d.45 A

解析

Continuous loads require 125% sizing: 40 A x 1.25 = 50 A for the conductors and overcurrent device.

法律依据: 2023 NEC 210.20(A)

免费刷完整 110 道题库 — 无需注册。

同考点相关题目

最近核对: · 审核流程

PrepPass 编辑团队 · 依据官方资料核对 Master Electrician Licensing Exam (NEC-based) · 我们如何核对