Design & Sizing第 25 / 110 题
A sewage ejector pump must handle a building with a discharge of 30 gpm against 18 ft of total head. Using WHP = (gpm x head in ft) / 3,960, what is the water horsepower?
a.0.14 hp
b.0.07 hp
c.0.10 hp
d.0.27 hp
解析
WHP = (30 x 18) / 3,960 = 540 / 3,960 = 0.136 hp, about 0.14 hp. The 3,960 constant is used when head is expressed in feet rather than psi. As with any pump, the motor is oversized above this by dividing by the pump efficiency.
法律依据: IPC §712.0免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A booster pump adds 52 psi. What is the equivalent head, in feet, that the pump develops? Use 1 psi = 2.31 ft of head.
- A recirculation loop must deliver 6 gpm of hot water. Using v = 0.408 x Q / d^2, what inside diameter keeps the velocity at about 2 ft/s to limit erosion of the continuously circulated hot line?
- A water main runs 250 ft of developed length and the friction chart shows a loss of 6 psi per 100 ft at the design flow. How much pressure is lost to friction over the full run?
- A sewage sump receiving a peak inflow of 45 gpm is served by a pump that discharges 90 gpm when running. If useful storage between pump-on and pump-off is 30 gallons, how long does one pump-down cycle (running time) last during peak inflow?
- Two demand loads combine on a main: branch A carries 40 WSFU and branch B carries 60 WSFU. If the Hunter demand chart converts 100 WSFU (predominantly flush tanks) to about 44 gpm, what design flow sizes the main?
- A meter and service must supply 44 gpm. The static supply is 68 psi, elevation loss is 20 psi, the meter loss is 8 psi, and the most remote fixture needs 15 psi. How much pressure remains for pipe friction?