A boiler feed with chemical treatment connects to potable water. This is a high-hazard connection. Which assembly protects the potable supply against backpressure from the pressurized boiler?
a.Atmospheric vacuum breaker
b.Dual check valve
c.Hose-bibb vacuum breaker
d.Reduced-pressure principle backflow assembly
解析
A chemically treated boiler is a high health hazard under backpressure, so a reduced-pressure principle assembly is required because it alone protects against backpressure of a health hazard. Atmospheric vacuum breakers cannot be used under continuous pressure or against backpressure. The RP relief port provides a visible, fail-safe break.
法律依据: UPC §603.5.7免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- An oil-water separator serves three garage floor drains each rated at 20 gpm. The code allows sizing at 75 percent of the total connected flow for diversity. What design flow sizes the separator?
- A laboratory discharges 10 gpm of acid waste that must be diluted with water at a 5-to-1 ratio (water to acid waste) before it enters the neutralizing tank. How much dilution water is required?
- An air admittance valve (AAV) is used to vent an island fixture. Which condition must be met for the AAV to be acceptable?
- A single-family residence has an underground lawn sprinkler system with no chemical injection and no downstream pressure. This is a low-hazard, backsiphonage-only condition. Which is the minimum acceptable backflow device?
- A water heater relief-valve discharge, softener drain, and condensate line all terminate at the same floor-level receptor. What must be true of the receptor and each connection?
- An air gap at a lavatory faucet must be maintained above the flood-level rim. If the effective opening of the faucet is 1/2 in and the outlet is near a single wall, the required gap is three times the opening. What is the minimum air gap?