Gas & Fuel第 59 / 110 题

A gas system serves a longest run of 80 ft to the most remote appliance, which needs 90 cfh. The table for 80 ft gives 3/4 in = 82 cfh and 1 in = 155 cfh. What size serves that final branch?

a.1/2 in
b.3/4 in
c.1 in
d.1-1/4 in

解析

At the 80 ft longest length, 90 cfh exceeds the 82 cfh capacity of 3/4 in pipe, so 1 in (155 cfh) is required. In the longest-length method every section of the system is sized using the single longest run, not each section's own length. This conservative method avoids undersizing under worst-case simultaneous demand.

法律依据: IFGC §402.4

免费刷完整 110 道题库 — 无需注册。

同考点相关题目

最近核对: · 审核流程

PrepPass 编辑团队 · 依据官方资料核对 Master Plumber Licensing Exam (UPC/IPC-based) · 我们如何核对