After a Manual J load is calculated, which ACCA procedure is used to select the specific equipment model?
a.Manual D
b.Manual T
c.Manual S
d.Manual RS
解析
Manual S matches equipment to the Manual J loads using manufacturer expanded performance data at local design conditions. It ensures the unit meets both sensible and latent loads without gross oversizing. Oversized equipment short-cycles and dehumidifies poorly.
免费刷完整 110 道题库 — 无需注册。