Branch Circuits & Feeders第 1 / 120 题
A 208-volt, single-phase branch circuit supplies a continuous load of 24 amperes. What is the minimum standard overcurrent device rating permitted?
a.30 amperes
b.25 amperes
c.24 amperes
d.40 amperes
解析
An overcurrent device supplying a continuous load must be rated at not less than 125 percent of that load: 24 A x 1.25 = 30 A, which is a standard rating in 240.6(A). The 24 A and 25 A choices ignore or under-apply the 125 percent factor, and 40 A jumps past the next standard size above the calculated value.
法律依据: 2023 NEC §210.20(A)免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- For that same 24-ampere continuous load, what is the minimum size copper branch-circuit conductor, assuming 75 degrees C terminations and THWN insulation?
- Six current-carrying 12 AWG THHN copper conductors are installed in a single EMT run at a 30 degrees C ambient. What is the adjusted ampacity of each conductor before termination limits are applied?
- Four current-carrying 8 AWG THWN-2 copper conductors run in a raceway through a 48 degrees C ambient. What is the adjusted ampacity of each conductor?
- A 120-volt circuit carries 20 amperes through 12 AWG copper (6,530 circular mils) to a load 100 feet away. Using K = 12.9, what is the approximate voltage drop?
- A 480-volt, three-phase feeder carries 40 amperes 250 feet using 6 AWG copper (26,240 circular mils). Using K = 12.9, what is the approximate voltage drop?
- A 120-volt branch circuit must carry 12 amperes 120 feet with voltage drop held to 3 percent. Using K = 12.9 for copper, what is the smallest conductor that meets the target?