Journeyman Electrician (NEC) Practice Test

想按顺序系统学?

练习一直免费。完整的 Journeyman Electrician (NEC) 学习指南是知识本身,从头到尾讲清楚 —— 可下载的 PDF + EPUB,永久归你。

获取本书 —— $14.99

常见问题

这里有多少道 Journeyman Electrician (NEC) 练习题?+

一整套原创 Journeyman Electrician (NEC) 练习题,覆盖官方内容板块、按真实考试权重分布、附解析。免费,无需注册。

Journeyman Electrician (NEC) 考试是什么样的?+

大约 161 道题、240 分钟、需 70% 及格。先在这里按主题刷题,再做完整计时模考检验准备度。

这些是真实考题吗?+

不是。每道题都是 100% 原创,依据公开一手来源编写并附解析。我们从不抄袭真题或付费备考资料。

我可以用中文或西班牙语学吗?+

PrepPass 练习提供英文、中文、西班牙文。官方考试以英文进行 —— 你随时可以把题目语言切回英文,熟悉考试当天的确切术语。

样题与解析

以下是本题库中的部分真题与完整解析。完整题库请用上方的刷题工具。

  1. 1. Branch Circuits & Feeders

    A 208-volt, single-phase branch circuit supplies a continuous load of 24 amperes. What is the minimum standard overcurrent device rating permitted?

    • a.30 amperes
    • b.25 amperes
    • c.24 amperes
    • d.40 amperes

    答案: a

    解析: An overcurrent device supplying a continuous load must be rated at not less than 125 percent of that load: 24 A x 1.25 = 30 A, which is a standard rating in 240.6(A). The 24 A and 25 A choices ignore or under-apply the 125 percent factor, and 40 A jumps past the next standard size above the calculated value.

    依据: 2023 NEC §210.20(A)

  2. 2. Services, Grounding & Bonding

    A service is supplied by two parallel sets of 250 kcmil copper conductors per phase. What is the minimum size copper grounding electrode conductor?

    • a.4 AWG
    • b.2 AWG
    • c.1/0 AWG
    • d.3/0 AWG

    答案: c

    解析: With parallel conductors the equivalent area is the sum of the areas in one phase: 2 x 250 kcmil = 500 kcmil, which falls in the over 350 through 600 kcmil row and requires 1/0 copper. Using 2 AWG treats a single 250 kcmil conductor as the whole service, and 3/0 corresponds to services above 1,100 kcmil.

    依据: 2023 NEC Table 250.66

  3. 3. Wiring Methods & Materials

    A short raceway nipple no longer than 24 inches connects two enclosures. What fill percentage is permitted?

    • a.31 percent
    • b.40 percent
    • c.53 percent
    • d.60 percent

    答案: d

    解析: Notes to Chapter 9, Table 1 permit a nipple not exceeding 24 inches in length to be filled to 60 percent of its total cross-sectional area, because heat buildup and pulling friction are both minimal over such a short run. The 40, 53 and 31 percent values are the normal fills for three or more, one, and two conductors respectively.

    依据: 2023 NEC Chapter 9, Table 1, Note 4

  4. 4. Motors & Equipment

    A continuous-duty motor over 1 horsepower has no marked service factor and no marked temperature rise. What is the maximum overload device rating as a percentage of nameplate full-load current?

    • a.140 percent
    • b.125 percent
    • c.115 percent
    • d.175 percent

    答案: c

    解析: Motors that carry neither a service factor of 1.15 or greater nor a marked temperature rise of 40 degrees C or less are limited to 115 percent of nameplate current, because there is less thermal margin available. The 125 percent value applies to the better-rated motors, 140 percent is the permitted increase when the motor will not start, and 175 percent is a fuse sizing percentage.

    依据: 2023 NEC §430.32(A)(1)

  5. 5. Branch Circuits & Feeders

    A dwelling has a single household electric clothes dryer with a nameplate rating of 4.5 kilowatts. What value must be used for the dryer load in the service calculation?

    • a.4,500 volt-amperes
    • b.4,000 volt-amperes
    • c.5,000 volt-amperes
    • d.3,600 volt-amperes

    答案: c

    解析: The load for a household electric clothes dryer is 5,000 volt-amperes or the nameplate rating, whichever is larger, so a 4,500-volt-ampere nameplate is calculated at the 5,000-volt-ampere floor. Using the nameplate 4,500 value violates the minimum, and the other figures apply factors that do not belong here.

    依据: 2023 NEC §220.54

  6. 6. Theory & Safety

    As defined in Article 100, ampacity is best described as which of the following?

    • a.The maximum current a conductor can carry continuously under the conditions of use without exceeding its temperature rating
    • b.The current that will instantly melt the conductor
    • c.The rated current of the overcurrent device protecting the conductor, taken directly from the marking on the breaker or fuse without regard to installation conditions
    • d.The current at which voltage drop reaches 3 percent

    答案: a

    解析: Article 100 defines ampacity as the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. It is a property of the conductor and its environment, not the rating of the protective device ahead of it.

    依据: 2023 NEC Art. 100

  7. 7. Branch Circuits & Feeders

    A 480-volt three-phase feeder carries 30 amperes 300 feet on 4 AWG copper (41,740 circular mils). Using K = 12.9, what is the approximate voltage drop?

    • a.4.8 volts
    • b.9.6 volts
    • c.5.6 volts
    • d.2.8 volts

    答案: a

    解析: Three-phase VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 30 x 300) / 41,740, about 4.8 V. Using 2 instead of 1.732 gives the 5.6-V answer. See NEC Chapter 9, Table 8.

  8. 8. Services, Grounding & Bonding

    A service uses two parallel sets of 600 kcmil copper conductors per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?

    • a.2/0 AWG
    • b.4/0 AWG
    • c.3/0 AWG
    • d.250 kcmil

    答案: c

    解析: Where copper service conductors exceed 1,100 kcmil, the main bonding jumper must be at least 12.5 percent of that area: 2 x 600 = 1,200 kcmil, and 1,200 x 0.125 = 150 kcmil. 2/0 (133.1 kcmil) is too small; 3/0 (167.8 kcmil) qualifies. See NEC 250.28(D)(2).

  9. 9. Wiring Methods & Materials

    A 15-ampere, 125-volt receptacle is installed in a damp location such as under a roofed open porch. What cover is required?

    • a.A cover that is weatherproof when no attachment plug is inserted
    • b.A cover that is weatherproof whether or not a plug is inserted
    • c.No cover is required in a damp location
    • d.A standard indoor wall plate

    答案: a

    解析: In damp locations a receptacle needs an enclosure weatherproof when a plug is not inserted; the stricter in-use cover, weatherproof with a plug inserted, is required in wet locations. See NEC 406.9(A).

  10. 10. Wiring Methods & Materials

    Type NM cable entering a single-gang nonmetallic box that has no cable clamps must be secured within what distance of the box?

    • a.24 inches
    • b.8 inches
    • c.3 feet
    • d.4 and 1/2 feet

    答案: b

    解析: Where a single-gang nonmetallic box without internal clamps is used, the NM cable must be secured within 8 inches of the box. See NEC 314.17(C) Exception and 334.30(A).

拥有完整的 Journeyman Electrician (NEC) 学习指南 —— PDF + EPUB,$14.99 →

反馈