Theory & Safety第 111 / 120 题
A balanced three-phase load draws 40 amperes at 480 volts with a power factor of 0.85. What is the true power?
a.Approximately 33.3 kilowatts
b.Approximately 28.3 kilowatts
c.Approximately 19.2 kilowatts
d.Approximately 16.3 kilowatts
解析
True power for a three-phase load is P = 1.732 x E x I x PF = 1.732 x 480 x 40 x 0.85, or about 28,270 watts. The 33.3-kilowatt answer omits the power factor and gives apparent power in kVA instead, 19.2 kilowatts leaves out the 1.732 factor, and 16.3 kilowatts omits both.
免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- How much power is dissipated when 5 amperes flows through a 20-ohm resistor?
- Three resistors of 10, 15 and 25 ohms are connected in series across 120 volts. What is the circuit current?
- A 20-ohm resistor and a 30-ohm resistor are connected in parallel. What is the total resistance?
- On a 208Y/120-volt wye system, what is the relationship between line voltage and phase voltage?
- A balanced delta-connected load has a phase current of 20 amperes. What is the line current?
- A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?