A feeder supplies a 100-ampere continuous load. Using 75 degrees C terminations and copper THWN, what is the minimum feeder conductor size?

a.1 AWG
b.2 AWG
c.1/0 AWG
d.3 AWG

解析

The feeder conductor must have an ampacity of at least 100 x 1.25 = 125 A. In the 75 degrees C column, 2 AWG copper is 115 A and falls short, while 1 AWG copper is 130 A and satisfies the requirement. 1/0 AWG at 150 A is larger than necessary, and 3 AWG at 100 A does not cover the continuous-load multiplier.

法律依据: 2023 NEC §215.2(A)(1)

免费刷完整 120 道题库 — 无需注册。