Branch Circuits & Feeders第 21 / 120 题
For that same 45-ampere continuous lighting feeder, what is the minimum copper conductor size at 75 degrees C terminations?
a.6 AWG
b.8 AWG
c.4 AWG
d.10 AWG
解析
The conductor must carry 45 x 1.25 = 56.25 A. In the 75 degrees C column, 8 AWG copper is 50 A and is insufficient, while 6 AWG copper at 65 A meets the requirement. 4 AWG is oversized for the stated minimum, and 10 AWG at 35 A is far below the calculated ampacity.
法律依据: 2023 NEC §215.2(A)(1)免费刷完整 120 道题库 — 无需注册。