Wiring Methods & Materials第 59 / 120 题
A box contains six 12 AWG conductors, one internal cable clamp and one duplex receptacle, all 12 AWG. What minimum box volume is required?
a.20.25 cubic inches
b.13.5 cubic inches
c.18.0 cubic inches
d.22.5 cubic inches
解析
Count six conductors, one allowance for all internal clamps and two allowances for the device yoke, giving 9 volume allowances. Each 12 AWG allowance is 2.25 cubic inches, so 9 x 2.25 = 20.25 cubic inches. Counting only the conductors gives 13.5 cubic inches, and forgetting that a yoke counts as two conductors gives 18.0 cubic inches.
法律依据: 2023 NEC §314.16(B)免费刷完整 120 道题库 — 无需注册。