Wiring Methods & Materials第 79 / 120 题
How many 12 AWG conductors may be installed in a 4-11/16 inch by 2-1/8 inch square box with a volume of 42.0 cubic inches, assuming no clamps, devices or fittings?
a.21
b.20
c.16
d.18
解析
Each 12 AWG conductor requires 2.25 cubic inches, so 42.0 / 2.25 = 18.67, and the count must be rounded down to 18 whole conductors. The 21-conductor answer uses the 14 AWG allowance of 2.00 cubic inches, and 20 comes from rounding up rather than down.
法律依据: 2023 NEC §314.16(A)免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A pull box is used for a straight pull, and the largest raceway entering it is 3 inch trade size. What is the minimum required length of the box in the direction of the pull?
- An angle pull box has one 2-inch raceway and one 1-inch raceway entering the same wall, with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
- How must liquidtight flexible metal conduit be secured on a normal run?
- Direct-buried conductors emerging from grade must be protected by an approved enclosure or raceway from below grade to what height?
- What is the maximum fill percentage when exactly two conductors are installed in a raceway?
- What is the minimum trade size of EMT required for twenty-four 12 AWG THHN conductors?