Water Supply & Distribution第 44 / 120 题
A fire sprinkler system with no antifreeze or chemical additives is connected to the potable water supply under continuous pressure. Which assembly is the appropriate minimum protection for this low hazard connection?
a.Atmospheric vacuum breaker
b.Pressure vacuum breaker
c.Reduced pressure principle assembly
d.Double check valve assembly
解析
A non-additive sprinkler system is a low hazard (pollutant, not contaminant) connection under continuous pressure, which is the exact application for a double check valve assembly. A reduced pressure assembly exceeds the minimum required here and adds an unnecessary relief discharge. An atmospheric vacuum breaker may never be used under continuous pressure, and a pressure vacuum breaker protects against back-siphonage only, not back-pressure.
法律依据: IPC §608.13免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- To limit erosion-corrosion and noise, what is the generally accepted maximum design velocity in a copper hot water distribution line?
- A commercial kitchen is being piped with solenoid-operated quick-closing valves on the dishwasher and ice machine supplies. What does the code require on those branches?
- A potable water line supplies makeup water to a chemically treated boiler system and the connection is under continuous pressure. Which backflow prevention device is required?
- An atmospheric vacuum breaker serves a fixture whose flood level rim is 34 in above the finished floor. What is the minimum height above the floor at which the vacuum breaker may be installed?
- A pressure vacuum breaker protects a lawn irrigation zone whose highest sprinkler head is 42 in above grade. What is the minimum height above grade for the vacuum breaker?
- Which condition makes a pressure vacuum breaker an unacceptable choice for a given cross-connection?