Water Supply & Distribution第 41 / 120 题
To limit erosion-corrosion and noise, what is the generally accepted maximum design velocity in a copper hot water distribution line?
a.5 feet per second
b.8 feet per second
c.10 feet per second
d.12 feet per second
解析
Hot water accelerates erosion of the copper tube wall, so hot lines are held to about 5 fps while cold lines are commonly designed to about 8 fps. The 8 fps answer is the cold water limit and is too aggressive for hot water. The 10 and 12 fps values are well above accepted design practice for any copper water line and would produce velocity noise and premature pinhole failures.
免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A 40 ft horizontal run of 3/4 in copper water tube is installed in a ceiling. Using a maximum horizontal support spacing of 6 ft for copper 1-1/2 in and smaller, what is the minimum number of hangers required?
- A 24 ft horizontal run of 1/2 in CPVC water distribution pipe is supported at the maximum spacing of 3 ft. What is the minimum number of supports required?
- PEX tubing runs horizontally for 16 ft above a suspended ceiling. Using the maximum horizontal support spacing of 32 in for PEX, what is the minimum number of supports?
- A commercial kitchen is being piped with solenoid-operated quick-closing valves on the dishwasher and ice machine supplies. What does the code require on those branches?
- A potable water line supplies makeup water to a chemically treated boiler system and the connection is under continuous pressure. Which backflow prevention device is required?
- A fire sprinkler system with no antifreeze or chemical additives is connected to the potable water supply under continuous pressure. Which assembly is the appropriate minimum protection for this low hazard connection?