Water Supply & Distribution第 56 / 120 题
What is the minimum nominal size normally permitted for a water service pipe serving a building?
a.1/2 in
b.5/8 in
c.1 in
d.3/4 in
解析
The water service pipe may not be smaller than 3/4 in regardless of what the fixture unit calculation produces. A 1/2 in service is below the code floor even for a very small single-fixture building, and 5/8 in is a meter size designation, not a standard pipe size. Requiring 1 in as the minimum is stricter than the code and would be a design choice, not a code requirement.
免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A sizing problem leaves 24 psi available for friction loss. The measured developed length to the most remote fixture is 160 ft, and fittings are estimated to add 50 percent to that length. What is the allowable friction loss per 100 ft of pipe?
- A dwelling unit contains one flush tank water closet (2.5 WSFU), two lavatories (1.0 WSFU each), one bathtub with shower (4.0 WSFU), one kitchen sink (1.5 WSFU), one dishwasher (1.5 WSFU), and one clothes washer (4.0 WSFU). What is the total water supply fixture unit load?
- Using the standard fixture unit to gpm conversion curve, what happens to the estimated demand when the total water supply fixture unit load on a system is doubled?
- The highest fixture in a building is 28 ft above the meter and requires 15 psi residual. Meter loss is 5 psi and calculated friction loss in the piping is 12 psi. What minimum static pressure is needed at the meter?
- Using velocity (fps) = 0.408 x flow (gpm) divided by the square of the inside diameter (in), what is the velocity of 12 gpm flowing in 3/4 in Type L copper with an inside diameter of 0.785 in?
- A 60 ft straight run of CPVC hot water pipe will see a 70 degree F temperature change. Using a coefficient of thermal expansion of 0.000034 in per in per degree F, approximately how much will the run expand?