Water Supply & Distribution第 53 / 120 题
A sizing problem leaves 24 psi available for friction loss. The measured developed length to the most remote fixture is 160 ft, and fittings are estimated to add 50 percent to that length. What is the allowable friction loss per 100 ft of pipe?
a.About 15 psi per 100 ft
b.About 6.7 psi per 100 ft
c.About 10 psi per 100 ft
d.About 24 psi per 100 ft
解析
Total equivalent length is 160 x 1.5 = 240 ft, so 24 psi / 240 ft x 100 = 10 psi per 100 ft. The 15 psi answer divides by the measured 160 ft and skips the fitting allowance. The 6.7 psi answer overstates the equivalent length, and 24 psi per 100 ft simply restates the total budget without dividing by length.
法律依据: UPC §610.0免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- What is the maximum weighted average lead content permitted on the wetted surfaces of pipe, fittings, and fixtures used to convey water for human consumption?
- Static pressure at the main is 72 psi. Meter loss at design flow is 9 psi, the highest fixture is 26 ft above the meter, and 15 psi residual is required at that fixture. How much pressure is available to overcome friction loss in the piping?
- A flushometer water closet on the top floor requires 20 psi residual. Static pressure is 65 psi, combined meter and backflow preventer loss is 10 psi, and the flush valve is 34 ft above the meter. How much pressure remains for friction loss in the piping and fittings?
- A dwelling unit contains one flush tank water closet (2.5 WSFU), two lavatories (1.0 WSFU each), one bathtub with shower (4.0 WSFU), one kitchen sink (1.5 WSFU), one dishwasher (1.5 WSFU), and one clothes washer (4.0 WSFU). What is the total water supply fixture unit load?
- Using the standard fixture unit to gpm conversion curve, what happens to the estimated demand when the total water supply fixture unit load on a system is doubled?
- What is the minimum nominal size normally permitted for a water service pipe serving a building?