Water Supply & Distribution第 60 / 120 题
An existing galvanized steel water line is being extended with copper tube. What must be installed at the point where the two materials join?
a.A brass compression coupling
b.An approved dielectric fitting or dielectric union
c.A soldered joint made directly to the steel pipe
d.A rubber sleeve coupling with stainless steel clamps
解析
Copper and galvanized steel are far apart on the galvanic scale, so a dielectric fitting is required to break the metallic path and prevent accelerated corrosion at the joint. A brass coupling still conducts and only shifts the corrosion cell rather than stopping it. Copper cannot be soldered directly to galvanized steel, and a rubber sleeve coupling is a drainage fitting that is not rated for water distribution pressure.
法律依据: IPC §605免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A dwelling unit contains one flush tank water closet (2.5 WSFU), two lavatories (1.0 WSFU each), one bathtub with shower (4.0 WSFU), one kitchen sink (1.5 WSFU), one dishwasher (1.5 WSFU), and one clothes washer (4.0 WSFU). What is the total water supply fixture unit load?
- Using the standard fixture unit to gpm conversion curve, what happens to the estimated demand when the total water supply fixture unit load on a system is doubled?
- What is the minimum nominal size normally permitted for a water service pipe serving a building?
- The highest fixture in a building is 28 ft above the meter and requires 15 psi residual. Meter loss is 5 psi and calculated friction loss in the piping is 12 psi. What minimum static pressure is needed at the meter?
- Using velocity (fps) = 0.408 x flow (gpm) divided by the square of the inside diameter (in), what is the velocity of 12 gpm flowing in 3/4 in Type L copper with an inside diameter of 0.785 in?
- A 60 ft straight run of CPVC hot water pipe will see a 70 degree F temperature change. Using a coefficient of thermal expansion of 0.000034 in per in per degree F, approximately how much will the run expand?