The same 175,000 Btu/h total connected load is served by LP-gas instead of natural gas. Using about 2,500 Btu per cubic foot for propane, what flow must the piping carry?
a.70 cfh
b.175 cfh
c.437 cfh
d.44 cfh
解析
For propane, cfh equals Btu/h divided by 2,500, so 175,000 / 2,500 = 70 cfh. 175 cfh is the natural gas answer using 1,000 Btu/cu ft; 437 cfh comes from multiplying instead of dividing by 2.5; 44 cfh comes from using a heating value near 4,000, which no common fuel gas has.
法律依据: IFGC §402.4免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A house is served with natural gas having a heating value of about 1,000 Btu per cubic foot. The connected appliances are a 100,000 Btu/h furnace, a 40,000 Btu/h water heater and a 35,000 Btu/h clothes dryer. What total flow, in cubic feet per hour, must the piping downstream of the meter carry?
- A natural gas system runs from the meter through section A (12 ft), then section B (18 ft), then section C (35 ft) to the farthest appliance. Using the longest developed length method, which length is used to select the size of section A?
- Measured along the pipe, the most remote gas outlet in a building is 78 ft from the meter. Sizing tables are printed in 10 ft length increments. Which length row should be used?
- A residential natural gas system is supplied at about 7 in w.c. from the utility meter. Which allowable pressure drop is normally used with the standard low-pressure sizing tables for this system?
- A gas furnace sits in a basement mechanical room. Its manual shutoff valve is installed in an adjacent storage room 9 ft away, behind a closed door. Why does this installation fail inspection?
- On which of the following appliances does the IFGC NOT require a sediment trap ahead of the appliance control valve?