Calculations第 5 / 110 题

What is the demand load for two 12-kW household electric ranges served from one feeder (range demand table, Column C, two appliances)?

a.11,000 VA
b.16,000 VA
c.12,000 VA
d.19,200 VA

解析

Two ranges not over 12 kW have a Column C demand of 11 kW = 11,000 VA. This is less than the 24,000 VA connected total because of diversity.