Master Electrician (NEC) — All Questions

这些题目考的数字,按章节排在可打印的彩色高密度页面上: 速记册,$9.99 →

拥有完整的 Master Electrician (NEC) 学习指南 —— PDF + EPUB,$14.99 →

← Back to practice

100 questions

Calculations

A single-family dwelling has 2,000 sq ft of habitable floor area. Using the standard calculation method at 3 VA per sq ft, what is the general lighting and general-use receptacle load before any demand factors?

  • a.3,000 VA
  • b.6,000 VA✓
  • c.4,000 VA
  • d.8,000 VA

General lighting is figured at 3 VA per sq ft: 2,000 sq ft x 3 VA = 6,000 VA. This value is calculated before applying the general-lighting demand factors.

Calculations

In the standard dwelling calculation, what is the minimum load to include for two required small-appliance branch circuits plus one laundry branch circuit, before any demand factor?

  • a.1,500 VA
  • b.4,500 VA✓
  • c.6,000 VA
  • d.3,000 VA

Each small-appliance and laundry circuit is figured at 1,500 VA. Two small-appliance circuits (2 x 1,500 = 3,000) plus one laundry circuit (1,500) equals 4,500 VA.

Calculations

A dwelling has 7,200 VA general lighting, 3,000 VA small-appliance, and 1,500 VA laundry. Applying the standard demand factor (first 3,000 VA at 100%, remainder at 35%), what is the net general lighting load?

  • a.4,095 VA
  • b.11,700 VA
  • c.7,200 VA
  • d.6,045 VA✓

Sum = 7,200 + 3,000 + 1,500 = 11,700 VA. First 3,000 at 100% = 3,000; remaining 8,700 at 35% = 3,045. Net = 3,000 + 3,045 = 6,045 VA.

Calculations

Using the demand table for household electric ranges, what is the demand load for one 12-kW electric range in a dwelling (Column C, one appliance)?

  • a.9,600 VA
  • b.12,000 VA
  • c.6,000 VA
  • d.8,000 VA✓

For a single household range not over 12 kW, the Column C demand is 8 kW = 8,000 VA. The 12-kW nameplate is reduced to an 8-kW calculated demand for one range.

Calculations

What is the demand load for two 12-kW household electric ranges served from one feeder (range demand table, Column C, two appliances)?

  • a.11,000 VA✓
  • b.12,000 VA
  • c.19,200 VA
  • d.16,000 VA

Two ranges not over 12 kW have a Column C demand of 11 kW = 11,000 VA. This is less than the 24,000 VA connected total because of diversity.

Calculations

A single household range is rated 16 kW. Using the 5% increase per kW over 12 kW rule on the 8-kW base, what is the demand load?

  • a.9,600 VA✓
  • b.16,000 VA
  • c.10,400 VA
  • d.8,000 VA

16 kW is 4 kW over 12 kW, so add 5% x 4 = 20% to the 8-kW base: 8,000 x 1.20 = 9,600 VA.

Calculations

A dwelling has one 4-kW electric clothes dryer. What value must be used as the dryer demand load in the service calculation?

  • a.5,500 VA
  • b.4,500 VA
  • c.4,000 VA
  • d.5,000 VA✓

The dryer load is the nameplate rating or 5,000 VA, whichever is larger. Since 4,000 VA is below 5,000 VA, 5,000 VA must be used.2023 NEC 220.54

Calculations

A dwelling has four fastened-in-place appliances (dishwasher, disposal, water heater, compactor) totaling 6,000 VA. What is the demand load after applying the fastened-appliance demand factor?

  • a.3,000 VA
  • b.4,500 VA✓
  • c.6,000 VA
  • d.7,500 VA

Where four or more fastened-in-place appliances are on the same feeder, a 75% demand factor may be applied: 6,000 x 0.75 = 4,500 VA.2023 NEC 220.53

Calculations

A dwelling's total calculated load is 24,000 VA on a 240-V, single-phase service. What is the calculated service current?

  • a.167 A
  • b.100 A✓
  • c.120 A
  • d.83 A

Current equals volt-amperes divided by voltage: 24,000 VA / 240 V = 100 A.

Calculations

Using the 75 C column, what is the smallest copper conductor rated to carry a 100-A service load?

  • a.#2 AWG
  • b.#4 AWG
  • c.#3 AWG✓
  • d.#1 AWG

At 75 C, #4 Cu is rated 85 A and #3 Cu is rated 100 A. The #3 AWG copper is the smallest conductor that meets the 100-A requirement.2023 NEC Table 310.16

Calculations

For a 200-A dwelling service using the 83% conductor allowance, what is the smallest copper ungrounded conductor (75 C) permitted for the main power feeder?

  • a.#1/0 AWG
  • b.#3/0 AWG
  • c.#2/0 AWG✓
  • d.#4/0 AWG

200 A x 0.83 = 166 A required ampacity. At 75 C, #2/0 Cu is rated 175 A, which satisfies 166 A, so #2/0 is the smallest permitted.2023 NEC 310.12

Calculations

An electric range has a Column C demand of 8,000 VA. Using the 70% neutral demand for ranges, what is the range contribution to the feeder neutral load?

  • a.8,000 VA
  • b.5,600 VA✓
  • c.4,000 VA
  • d.7,000 VA

The feeder neutral for a household range may be figured at 70% of the range demand: 8,000 x 0.70 = 5,600 VA.

Calculations

From the motor full-load current table, what is the full-load current of a 25-HP, 480-V, three-phase induction motor?

  • a.28 A
  • b.42 A
  • c.34 A✓
  • d.40 A

The table value for a 25-HP, 460-480-V three-phase motor is 34 A. Table full-load current (FLC), not nameplate, is used for conductor and protection sizing.2023 NEC Table 430.250

Calculations

A single continuous-duty motor has a table full-load current of 34 A. What minimum conductor ampacity is required for its branch circuit?

  • a.50 A
  • b.34 A
  • c.40 A
  • d.42.5 A✓

Motor branch-circuit conductors must be at least 125% of the FLC: 34 A x 1.25 = 42.5 A minimum ampacity.2023 NEC 430.22

Calculations

A motor with a service factor of 1.15 has a nameplate full-load current of 34 A. What is the maximum overload protection setting at 125%?

  • a.42.5 A✓
  • b.45.9 A
  • c.34 A
  • d.39.1 A

For a motor with service factor 1.15 or greater, overload is set at up to 125% of nameplate FLA: 34 x 1.25 = 42.5 A.2023 NEC 430.32

Calculations

For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?

  • a.70 A
  • b.100 A
  • c.90 A✓
  • d.80 A

Inverse-time breaker: 250% of FLC = 34 x 2.50 = 85 A. Where this does not correspond to a standard size, the next higher standard rating (90 A) is permitted.2023 NEC 430.52

Calculations

A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?

  • a.110 A
  • b.92.5 A✓
  • c.105 A
  • d.84 A

Feeder ampacity = 125% of the largest motor FLC plus the sum of the others: (34 x 1.25) + 28 + 22 = 42.5 + 50 = 92.5 A.2023 NEC 430.24

Calculations

What is the full-load primary current of a 75-kVA, 480-V, three-phase transformer?

  • a.72 A
  • b.104 A
  • c.90 A✓
  • d.156 A

Three-phase current = VA / (1.732 x V): 75,000 / (1.732 x 480) = 90.2 A, about 90 A.

Calculations

What is the full-load secondary current of a 75-kVA, three-phase transformer with a 208-V secondary?

  • a.208 A✓
  • b.180 A
  • c.156 A
  • d.90 A

Secondary current = 75,000 / (1.732 x 208) = 208.2 A, about 208 A.

Calculations

A 75-kVA transformer has a 90-A primary current (over 9 A). With primary-only protection at 125% max, what is the primary overcurrent device rating (next higher standard permitted)?

  • a.150 A
  • b.100 A
  • c.125 A✓
  • d.110 A

125% of 90 A = 112.5 A. Where this does not match a standard rating, the next higher standard device (125 A) is permitted for primary-only protection.2023 NEC 450.3(B)

Calculations

A 120-V branch circuit carries 16 A over a one-way run of 80 ft using #12 Cu (circular mils = 6,530, K = 12.9). What is the approximate voltage drop?

  • a.5.1 V✓
  • b.7.4 V
  • c.3.0 V
  • d.2.5 V

Single-phase VD = (2 x K x I x L) / CM = (2 x 12.9 x 16 x 80) / 6,530 = 33,024 / 6,530 = 5.06 V.

Calculations

Using the previous circuit (5.06-V drop on a 120-V circuit), what is the approximate percent voltage drop?

  • a.3.0%
  • b.6.0%
  • c.4.2%✓
  • d.2.1%

Percent VD = 5.06 / 120 = 0.042 = 4.2%, which exceeds the 3% recommended for branch circuits.

Calculations

A 208-V three-phase feeder carries 40 A over 150 ft using #6 Cu (CM = 26,240, K = 12.9). What is the approximate voltage drop?

  • a.3.0 V
  • b.7.2 V
  • c.9.0 V
  • d.5.1 V✓

Three-phase VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 40 x 150) / 26,240 = 134,050 / 26,240 = 5.11 V.

Calculations

For a 112.5-kVA, 208-V, three-phase transformer with 2% impedance, what is the approximate available fault current at the secondary terminals (infinite primary)?

  • a.15,617 A✓
  • b.20,000 A
  • c.6,250 A
  • d.10,000 A

Secondary FLA = 112,500 / (1.732 x 208) = 312.3 A. Isc = FLA / %Z = 312.3 / 0.02 = 15,617 A.

Calculations

A 45-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary (infinite primary)?

  • a.12,500 A
  • b.3,120 A
  • c.6,245 A✓
  • d.9,000 A

Secondary FLA = 45,000 / (1.732 x 208) = 124.9 A. Isc = 124.9 / 0.02 = 6,245 A.

Calculations

Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?

  • a.55 A
  • b.60 A✓
  • c.52.5 A
  • d.75 A

For 4 to 6 current-carrying conductors, apply an 80% adjustment factor: 75 A x 0.80 = 60 A.2023 NEC Table 310.15(C)(1)

Calculations

A #3 Cu THHN conductor has a 90 C ampacity of 110 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?

  • a.90 A✓
  • b.82 A
  • c.100 A
  • d.110 A

Corrected ampacity = 110 A x 0.82 = 90.2 A, about 90 A, before comparing to the termination temperature limit.2023 NEC Table 310.15(B)(1)

Calculations

A #2 Cu THHN (90 C ampacity 130 A) runs with 6 current-carrying conductors (0.80 factor) in a 40 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?

  • a.130 A
  • b.95 A✓
  • c.104 A
  • d.115 A

Apply both factors to the 90 C ampacity: 130 x 0.80 x 0.91 = 94.6 A, about 95 A.

Calculations

An office has 45 general-use receptacle outlets. At 180 VA per outlet, what is the receptacle load before demand factors?

  • a.5,400 VA
  • b.4,500 VA
  • c.9,000 VA
  • d.8,100 VA✓

Each general-use receptacle outlet is figured at 180 VA: 45 x 180 = 8,100 VA.2023 NEC 220.14(I)

Calculations

A commercial building has a 30,000-VA receptacle load. Applying the demand (first 10 kVA at 100%, remainder at 50%), what is the demand load?

  • a.25,000 VA
  • b.15,000 VA
  • c.30,000 VA
  • d.20,000 VA✓

First 10,000 VA at 100% = 10,000; remaining 20,000 at 50% = 10,000. Total demand = 20,000 VA.

Calculations

A one-family dwelling has a total general load (lighting, small-appliance, laundry, fastened appliances, ranges) of 40,000 VA before HVAC. Using the optional method of 220.82(B), what is the demand for these general loads?

  • a.22,000 VA✓
  • b.16,000 VA
  • c.40,000 VA
  • d.28,000 VA

2023 NEC 220.82(B) takes 100% of the first 10 kVA plus 40% of the remainder: 10,000 + 0.40 x 30,000 = 10,000 + 12,000 = 22,000 VA. Trap: 16,000 VA applies 40% to the whole 40,000; the first 10 kVA must stay at 100%.2023 NEC 220.82(B)

Calculations

Under the optional dwelling calculation, central electric space-heating load is included at what percent of nameplate?

  • a.100%
  • b.65%✓
  • c.40%
  • d.75%

2023 NEC 220.82(C)(3) permits central electric space heating at 65% of nameplate. Trap: the 40% figure (220.82(C)(5)) applies only to four or more separately controlled electric-heat units, not to central heat.2023 NEC 220.82(C)

Calculations

A 10,000 sq ft office building is calculated for general lighting using the 2023 unit-load table for office/bank occupancies. What is the general lighting load?

  • a.25,000 VA
  • b.20,000 VA
  • c.30,000 VA
  • d.35,000 VA✓

2023 NEC Table 220.42(A) lists 3.5 VA per sq ft for banks and office buildings: 10,000 x 3.5 = 35,000 VA. Trap: 30,000 VA uses the 3 VA/sq ft dwelling/store value.2023 NEC Table 220.42(A)

Calculations

A 6,000 sq ft retail store is calculated for general lighting using the 2023 unit-load table. What is the general lighting load?

  • a.18,000 VA✓
  • b.12,000 VA
  • c.21,000 VA
  • d.15,000 VA

2023 NEC Table 220.42(A) lists 3 VA per sq ft for stores: 6,000 x 3 = 18,000 VA. Trap: 21,000 VA mistakenly uses the 3.5 VA/sq ft office value.2023 NEC Table 220.42(A)

Calculations

A commercial service supplies several motors; the largest has a 40-A full-load current. How much is added to the service calculation for the largest-motor factor?

  • a.50 A
  • b.40 A
  • c.10 A✓
  • d.8 A

2023 NEC 430.24 (with 220.50) requires 25% of the largest motor FLC be added on top of the motor loads: 0.25 x 40 = 10 A. Trap: 50 A adds 125% of the motor, double-counting the FLC that is already in the load.2023 NEC 430.24

Calculations

A commercial kitchen has six kitchen-equipment units totaling 60 kW. Applying the demand factor for six or more units, what is the demand load?

  • a.60 kW
  • b.39 kW✓
  • c.45 kW
  • d.42 kW

2023 NEC Table 220.56 allows 65% for six or more units: 60 x 0.65 = 39 kW (result may not be less than the sum of the two largest units). Trap: 45 kW uses 75%, the four-appliance dwelling factor, not the commercial-kitchen table.2023 NEC 220.56

Calculations

Transformer secondary conductors run 8 ft to a panelboard under the 10-ft secondary rule. Their ampacity must be not less than:

  • a.10% of the primary overcurrent device rating
  • b.the primary conductor ampacity
  • c.the rating of the device or busbar they supply✓
  • d.at least 300% of the transformer's rated secondary current

2023 NEC 240.21(C)(2) allows unprotected secondary conductors up to 10 ft if their ampacity is at least the calculated load and at least the rating of the device or busbar they terminate in. Trap: the 1/10 rule belongs to the 10-ft feeder tap 240.21(B)(1), not the transformer-secondary rule.2023 NEC 240.21(C)(2)

Calculations

A 75-kVA, 480-208Y/120-V transformer feeds a panel through 20-ft secondary conductors under 240.21(C)(6). What is the minimum secondary conductor ampacity?

  • a.208 A✓
  • b.167 A
  • c.260 A
  • d.104 A

Secondary FLC = 75,000 / (1.732 x 208) = 208 A. 240.21(C)(6) requires the 20-ft secondary conductors to have ampacity at least equal to the transformer secondary current (208 A) and to terminate in a single OCPD not exceeding that ampacity. Trap: 260 A is 125% of secondary current, which would size the OCPD, not the minimum conductor.2023 NEC 240.21(C)(6)

Calculations

A 400-A feeder overcurrent device supplies a 10-ft tap. Under the 10-ft feeder tap rule, what minimum tap-conductor ampacity comes from the 1/10 provision?

  • a.200 A
  • b.133 A
  • c.13 A
  • d.40 A✓

2023 NEC 240.21(B)(1) requires the 10-ft tap ampacity to be at least 1/10 of the 400-A device: 400 / 10 = 40 A (and at least the load served). Trap: 133 A is the 1/3 value that belongs to the 25-ft tap rule 240.21(B)(2).2023 NEC 240.21(B)(1)

Calculations

A 600-A feeder overcurrent device supplies a 25-ft tap. Under the 25-ft feeder tap rule, what minimum tap-conductor ampacity is required?

  • a.60 A
  • b.200 A✓
  • c.300 A
  • d.150 A

2023 NEC 240.21(B)(2) requires the 25-ft tap ampacity to be at least 1/3 of the 600-A device: 600 / 3 = 200 A. Trap: 60 A applies the 1/10 rule, which is only for the 10-ft tap.2023 NEC 240.21(B)(2)

Calculations

A 75-kVA transformer with a 208-A secondary (over 9 A) is protected on both the primary and the secondary. What is the maximum secondary overcurrent device (next higher standard permitted)?

  • a.300 A✓
  • b.260 A
  • c.250 A
  • d.225 A

Table 450.3(B) allows up to 125% on the secondary where both sides are protected: 208 x 1.25 = 260 A. Since 260 A is not a standard size, Note 1 permits the next higher standard rating, 300 A. Trap: 250 A is the next lower standard and would be too small to carry full secondary load.2023 NEC 450.3(B)

Calculations

From the motor full-load current table, what is the full-load current of a 50-HP, 460-V, three-phase induction motor?

  • a.52 A
  • b.80 A
  • c.65 A✓
  • d.48 A

2023 NEC Table 430.250 lists 65 A for a 50-HP, 460-V three-phase motor. This table FLC (not nameplate) is used for branch-circuit and feeder sizing. Trap: 52 A is the 40-HP value.2023 NEC Table 430.250

Calculations

A motor with a 34-A full-load current is protected by a non-time-delay (one-time) fuse. At 300%, what is the maximum branch-circuit short-circuit/ground-fault fuse (next standard size)?

  • a.90 A
  • b.100 A
  • c.125 A
  • d.110 A✓

Table 430.52 allows 300% for non-time-delay fuses: 34 x 3.00 = 102 A. Where this is not a standard size, 430.52(C)(1) Exception 1 permits the next higher standard fuse, 110 A. Trap: a time-delay (dual-element) fuse uses only 175% (60 A).2023 NEC 430.52

Calculations

The optional calculation for a multifamily dwelling (220.84) may be used only where the building has at least how many dwelling units?

  • a.3✓
  • b.2
  • c.5
  • d.10

2023 NEC 220.84 applies to multifamily dwellings of three or more units that meet the stated conditions (single feeder per unit, electric cooking, and electric heat or air-conditioning). Trap: 5 confuses this with range-table diversity, not the unit-count threshold.2023 NEC 220.84

Calculations

A feeder supplies five household electric ranges, each rated 12 kW. Using Column C of the range demand table, what is the demand load?

  • a.17,000 VA
  • b.25,000 VA
  • c.20,000 VA✓
  • d.21,000 VA

2023 NEC Table 220.55, Column C, gives 20 kW for five ranges not over 12 kW: 20,000 VA. Trap: 21,000 VA is the six-range value; 25,000 VA wrongly prorates 5 x 5 kW.2023 NEC Table 220.55

Calculations

A service neutral carries a maximum unbalanced load of 250 A. Applying the neutral demand allowance, what is the calculated neutral load?

  • a.250 A
  • b.235 A✓
  • c.225 A
  • d.210 A

2023 NEC 220.61(B) permits 70% on the portion of neutral load over 200 A: 200 + 0.70 x 50 = 200 + 35 = 235 A. Trap: 250 A ignores the reduction; only the amount above 200 A is reduced.2023 NEC 220.61(B)

Calculations

When more than two conductors are pulled into a single conduit, what maximum percent of the conduit's cross-sectional area may they occupy?

  • a.53%
  • b.31%
  • c.60%
  • d.40%✓

2023 NEC Chapter 9, Table 1: over two conductors is limited to 40% fill. Trap: 53% is the limit for one conductor and 31% for exactly two.2023 NEC Chapter 9 Table 1

Calculations

A box contains eight #12 AWG conductors and nothing else. Using the box-fill volume allowance, what minimum box volume is required?

  • a.16.0 cu in
  • b.20.0 cu in
  • c.18.0 cu in✓
  • d.22.5 cu in

2023 NEC Table 314.16(B) assigns 2.25 cu in to each #12 conductor: 8 x 2.25 = 18.0 cu in. Trap: 16.0 uses the 2.0 cu in #14 value; 22.5 uses the 2.5 cu in #10 value.2023 NEC Table 314.16(B)

Calculations

Under the optional method for adding load to an existing dwelling (220.83), after taking 100% of the first 8 kVA, the remaining other loads are calculated at what percent?

  • a.40%✓
  • b.35%
  • c.50%
  • d.65%

2023 NEC 220.83(B) takes 100% of the first 8 kVA and 40% of the remainder of the other load where additional air-conditioning or space-heating is being added. Trap: 35% is the general-lighting remainder factor from the standard method 220.42, not 220.83.2023 NEC 220.83(B)

Calculations

A large multifamily building has 900,000 VA of connected load and an applicable 220.84 demand factor of 32%. What is the calculated demand load?

  • a.450,000 VA
  • b.900,000 VA
  • c.288,000 VA✓
  • d.360,000 VA

The optional multifamily method multiplies connected load by the Table 220.84 demand factor: 900,000 x 0.32 = 288,000 VA. Trap: 360,000 VA uses 40%; the demand factor falls as the number of units rises.2023 NEC 220.84

这门考试有多难?

电工技师(Master)执照由各州主办、以 NEC 为依据,因此格式因州而异。例如在德州,考试分两个开卷部分(2023 NEC)——75 道 NEC 知识题与 33 道计算题(共 108 题)——各须 70% 方可通过,费用 78 美元。电工年薪中位数约 62,350 美元(BLS,2024 年 5 月)。

推荐学习时间
多数人 80-150 小时——技师考试比熟练工增加更重的计算与规范应用深度。
官方公布的通过率
19.08% (来源未说明统计的是哪些考次)(n = 3,946);22.21% (来源未说明统计的是哪些考次)(n = 3,472) —— Texas TDLR,FY 2025。请把它们看作两场考试而非一场:TDLR 并没有名为「Master Electrician」的行,只有「Master Calculations」(第一个数字)和「Master NEC」(第二个数字)。任何引用单一「德州 master 通过率 19%」的说法,都悄悄丢掉了一半考试。执照按州发放,因此这只适用于德州。来源: Texas TDLR — Electrician Exam Statistics, Fiscal Year 2025
重点学习方向
服务、服务设备与单独派生系统是最重的板块之一(德州约 18%),外加负载计算部分。

费用与薪资为近似值,会随时间变动。上方的通过率引自旁边链接的来源,并限于该来源覆盖的期间——凡是我们尚未核实来源的,都会直接说明并且不给数字。

反馈