Design & Sizing第 11 / 110 题

A 2 in horizontal fixture drain must fall a total of 5 in over its run at the code minimum slope of 1/4 in per foot. How long is the run?

a.24 ft
b.40 ft
c.20 ft
d.60 ft

解析

Length = fall / slope = 5 in / (1/4 in per ft) = 5 x 4 = 20 ft. Pipe 2-1/2 in and smaller uses the steeper 1/4 in per foot minimum. Dividing by 1/8 in per ft would incorrectly give 40 ft, the rate reserved for 3 in and larger pipe.

法律依据: IPC §704.1

免费刷完整 110 道题库 — 无需注册。