A vent must be sized at not less than one-half the diameter of the drain it serves, and never smaller than 1-1/4 in. What is the minimum vent size for a 3 in drain?
a.1-1/4 in
b.2 in
c.3 in
d.1-1/2 in
解析
Half of 3 in is 1-1/2 in, which is larger than the 1-1/4 in floor, so the minimum vent is 1-1/2 in. The half-diameter rule sets the size and the 1-1/4 in minimum only governs very small drains. A 4 in drain by the same rule would need at least a 2 in vent.
法律依据: UPC §904.1免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A horizontal fixture branch carries 30 DFU. The sizing table lists these branch capacities: 2 in = 6 DFU, 3 in = 20 DFU, 4 in = 160 DFU. Two of the fixtures are water closets. What is the minimum pipe size for the branch?
- A 4 in building drain is run at the code minimum slope of 1/8 in per foot over a developed length of 96 ft. What is the total fall from the upstream end to the downstream end?
- A 2 in horizontal fixture drain must fall a total of 5 in over its run at the code minimum slope of 1/4 in per foot. How long is the run?
- A 2 in trap arm connects a fixture trap to its vent. The code limits the fall in a trap arm to no more than one pipe diameter between the trap weir and the vent. What is the maximum allowable fall in this trap arm?
- A natural-gas furnace is rated at 120,000 BTU/hr. Natural gas has a heating value of about 1,000 BTU per cubic foot. What gas volume flow, in cubic feet per hour (cfh), must the piping deliver?
- A house has three natural-gas appliances: a 100,000 BTU/hr furnace, a 40,000 BTU/hr water heater, and a 65,000 BTU/hr range. Using 1,000 BTU per cubic foot, what total cfh must the gas meter and main serve?