A house has three natural-gas appliances: a 100,000 BTU/hr furnace, a 40,000 BTU/hr water heater, and a 65,000 BTU/hr range. Using 1,000 BTU per cubic foot, what total cfh must the gas meter and main serve?
a.165 cfh
b.240 cfh
c.205 cfh
d.2,050 cfh
解析
Total input = 100,000 + 40,000 + 65,000 = 205,000 BTU/hr, and at 1,000 BTU per cubic foot that is 205 cfh. The whole-house demand sizes the meter and the main from the meter to the first tee. Individual branches are then sized for the appliance each one serves.
法律依据: IFGC §402.4免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A vent must be sized at not less than one-half the diameter of the drain it serves, and never smaller than 1-1/4 in. What is the minimum vent size for a 3 in drain?
- A 2 in trap arm connects a fixture trap to its vent. The code limits the fall in a trap arm to no more than one pipe diameter between the trap weir and the vent. What is the maximum allowable fall in this trap arm?
- A natural-gas furnace is rated at 120,000 BTU/hr. Natural gas has a heating value of about 1,000 BTU per cubic foot. What gas volume flow, in cubic feet per hour (cfh), must the piping deliver?
- A propane appliance is rated at 150,000 BTU/hr. Propane has a heating value of about 2,500 BTU per cubic foot. What is the required gas flow in cfh?
- A gas branch must deliver 55 cfh of natural gas over a 60 ft longest length. The sizing table for that length gives these capacities: 1/2 in = 42 cfh, 3/4 in = 88 cfh, 1 in = 165 cfh. What is the minimum pipe size?
- Using the rational method Q = 0.0104 x A x i, where A is the projected roof area in square feet and i is the rainfall rate in in/hr, what is the design storm flow for a 6,000 ft^2 roof at a 3 in/hr rainfall rate?