Design & Sizing第 16 / 110 题
A propane appliance is rated at 150,000 BTU/hr. Propane has a heating value of about 2,500 BTU per cubic foot. What is the required gas flow in cfh?
a.15 cfh
b.30 cfh
c.150 cfh
d.60 cfh
解析
cfh = 150,000 / 2,500 = 60 cfh. Propane packs about 2.5 times the energy of natural gas per cubic foot, so the same BTU load needs far fewer cubic feet, which is why propane piping is often smaller than natural-gas piping for the same appliance.
法律依据: IFGC §402.4免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A 2 in trap arm connects a fixture trap to its vent. The code limits the fall in a trap arm to no more than one pipe diameter between the trap weir and the vent. What is the maximum allowable fall in this trap arm?
- A natural-gas furnace is rated at 120,000 BTU/hr. Natural gas has a heating value of about 1,000 BTU per cubic foot. What gas volume flow, in cubic feet per hour (cfh), must the piping deliver?
- A house has three natural-gas appliances: a 100,000 BTU/hr furnace, a 40,000 BTU/hr water heater, and a 65,000 BTU/hr range. Using 1,000 BTU per cubic foot, what total cfh must the gas meter and main serve?
- A gas branch must deliver 55 cfh of natural gas over a 60 ft longest length. The sizing table for that length gives these capacities: 1/2 in = 42 cfh, 3/4 in = 88 cfh, 1 in = 165 cfh. What is the minimum pipe size?
- Using the rational method Q = 0.0104 x A x i, where A is the projected roof area in square feet and i is the rainfall rate in in/hr, what is the design storm flow for a 6,000 ft^2 roof at a 3 in/hr rainfall rate?
- A roof drains 4,800 ft^2 at a design rainfall rate of 4 in/hr. Using Q = 0.0104 x A x i, what is the storm design flow?