Decontamination第 5 / 100 题

A facility engineer asks what temperature range the decontamination area should be maintained within. What is the correct answer?

a.60 to 65 degrees F (16 to 18 degrees C)
b.68 to 73 degrees F (20 to 23 degrees C)
c.75 to 80 degrees F (24 to 27 degrees C)
d.Any temperature that staff find comfortable in personal protective equipment

解析

The decontamination area is kept cooler, roughly 60 to 65 degrees F, because staff work in full impervious personal protective equipment and the cooler air limits heat stress and microbial growth. The 68 to 73 degrees F range applies to the preparation and packaging area. Storage areas should not exceed about 75 degrees F, and comfort alone is not an acceptable engineering control.

法律依据: AAMI ST79

免费刷完整 100 道题库 — 无需注册。

同考点相关题目

最近核对: · 审核流程

PrepPass 编辑团队 · 依据官方资料核对 HSPA Certified Registered Central Service Technician (CRCST) Exam · 我们如何核对