Motors & Equipment第 100 / 120 题
A recessed luminaire that is NOT identified for insulation contact must maintain what minimum clearance from thermal insulation?
a.1 inch
b.1/2 inch
c.6 inches
d.3 inches
解析
A non-IC recessed luminaire must be spaced at least 3 inches from thermal insulation so heat can dissipate, and insulation must not be installed above it in a way that traps heat. The 1/2-inch dimension is the required clearance from combustible materials other than the mounting surface, which is a different measurement.
法律依据: 2023 NEC §410.116免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A hermetic refrigerant motor-compressor has a rated-load current of 20 amperes. What is the maximum branch-circuit short-circuit and ground-fault protective device at the standard 175 percent figure?
- For that same 20-ampere rated-load compressor supplied alone, what minimum conductor ampacity is required?
- A surface-mounted luminaire with a completely enclosed light source is installed in a clothes closet. What is the minimum clearance to the nearest point of the defined storage space?
- A generator nameplate current rating is 200 amperes. What minimum conductor ampacity is required from the generator terminals to the first overcurrent device?
- A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?
- A motor with a service factor of 1.16 will not start because the overload device trips, even though it is sized at 125 percent of nameplate current. To what maximum percentage may the overload device be increased?