56 questions

Motors & Equipment

A 25-horsepower, 460-volt, three-phase squirrel-cage motor has a table full-load current of 34 amperes. Using 75 degrees C terminations and copper, what is the minimum branch-circuit conductor size?

  • a.6 AWG
  • b.10 AWG
  • c.8 AWG
  • d.4 AWG

Single-motor branch-circuit conductors must carry at least 125 percent of the table full-load current: 34 x 1.25 = 42.5 A. In the 75 degrees C column, 10 AWG copper is 35 A and fails, while 8 AWG at 50 A is adequate. Sizes 6 and 4 AWG exceed the calculated minimum.2023 NEC §430.22

Motors & Equipment

That same motor has a nameplate full-load current of 32 amperes and a marked service factor of 1.15. What is the maximum separate overload device rating?

  • a.36.8 amperes
  • b.40 amperes
  • c.42.5 amperes
  • d.32 amperes

Overload protection is based on the nameplate current, not the table value, and a service factor of 1.15 or greater permits 125 percent: 32 x 1.25 = 40 A. The 36.8-ampere answer applies the 115 percent factor used for motors with no marked service factor or temperature rise, and 42.5 amperes wrongly applies 125 percent to the table value of 34 A.2023 NEC §430.32(A)(1)

Motors & Equipment

For that 34-ampere three-phase squirrel-cage motor, what is the maximum inverse-time circuit breaker permitted for branch-circuit short-circuit and ground-fault protection, using the next standard size allowance?

  • a.90 amperes
  • b.85 amperes
  • c.100 amperes
  • d.70 amperes

An inverse-time breaker is permitted at 250 percent of full-load current: 34 x 2.50 = 85 A, which is not a standard rating, so the next higher standard size of 90 amperes may be used. The 100-ampere answer skips a standard size, and 70 amperes corresponds to the 175 percent dual-element fuse calculation instead.2023 NEC Table 430.52(C)(1)

Motors & Equipment

For the same 34-ampere motor, what is the maximum dual-element time-delay fuse permitted at the standard percentage?

  • a.60 amperes
  • b.70 amperes
  • c.50 amperes
  • d.90 amperes

Dual-element time-delay fuses are permitted at 175 percent of full-load current: 34 x 1.75 = 59.5 A, and because that is not a standard rating the next standard size of 60 amperes is used. The 90-ampere answer belongs to the inverse-time breaker at 250 percent, and 50 amperes falls below the calculated value.2023 NEC Table 430.52(C)(1)

Motors & Equipment

A 5-horsepower, 230-volt single-phase motor has a table full-load current of 28 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?

  • a.10 AWG
  • b.12 AWG
  • c.8 AWG
  • d.6 AWG

The conductor must carry 28 x 1.25 = 35 A. In the 75 degrees C column, 10 AWG copper is exactly 35 A and qualifies, while 12 AWG at 25 A does not. Note that 240.4(D) limits ordinary 10 AWG circuits to a 30-ampere device, but motor branch-circuit protection is sized under Article 430 instead.2023 NEC §430.22

Motors & Equipment

A 30-horsepower, 460-volt three-phase motor has a table full-load current of 40 amperes. What is the minimum ampere rating of the disconnecting means?

  • a.50 amperes
  • b.40 amperes
  • c.46 amperes
  • d.60 amperes

The disconnecting means must have an ampere rating of at least 115 percent of the full-load current: 40 x 1.15 = 46 A, so a 60-ampere switch would be the practical selection. The 40-ampere answer omits the 115 percent factor entirely, and 50 or 60 amperes are available equipment ratings rather than the calculated minimum the question asks for.2023 NEC §430.110(A)

Motors & Equipment

A feeder supplies a 25-horsepower motor (34 amperes) and a 10-horsepower motor (14 amperes), both 460 volts three phase. What minimum conductor ampacity is required?

  • a.67.5 amperes
  • b.60 amperes
  • c.48 amperes
  • d.56.5 amperes

Feeder conductors for several motors must carry 125 percent of the largest motor full-load current plus the sum of the other full-load currents: (34 x 1.25) + 14 = 42.5 + 14 = 56.5 A. The 48-ampere answer simply adds the two currents, and 67.5 amperes wrongly applies 125 percent to the total of both motors.2023 NEC §430.24

Motors & Equipment

For that same two-motor feeder, if the largest branch-circuit protective device is 90 amperes, what is the maximum feeder overcurrent device rating?

  • a.90 amperes
  • b.104 amperes
  • c.110 amperes
  • d.100 amperes

The feeder device may not exceed the largest branch-circuit short-circuit and ground-fault protective device plus the sum of the full-load currents of the other motors: 90 + 14 = 104 A. Since 104 is not a standard rating and this is a maximum rather than a minimum, the next lower standard size of 100 amperes must be selected. Choosing 110 amperes would exceed the calculated ceiling.2023 NEC §430.62(A)

Motors & Equipment

When sizing motor branch-circuit conductors and short-circuit protection, which current value must be used?

  • a.The locked-rotor current from the nameplate code letter
  • b.The motor nameplate full-load amperes
  • c.The full-load current from Table 430.248 or 430.250
  • d.The larger of nameplate current or table current

Conductor sizing, branch-circuit protection and disconnect rating are all based on the table values, which are conservative and independent of a particular manufacturer's nameplate. Nameplate current is used only for overload protection under 430.32, and locked-rotor current is used for withstand and disconnect horsepower comparisons, not for conductor sizing.2023 NEC §430.6(A)(1)

Motors & Equipment

A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C but no service factor. What percentage of nameplate full-load current sets the maximum overload device?

  • a.140 percent
  • b.115 percent
  • c.125 percent
  • d.250 percent

Motors with a marked temperature rise not over 40 degrees C, like those with a service factor of 1.15 or greater, are permitted overload protection at 125 percent of nameplate current. The 115 percent figure applies to all other motors, 140 percent is the allowance when the initial setting will not carry the load, and 250 percent is a short-circuit protection value.2023 NEC §430.32(A)(1)

Motors & Equipment

A continuous-duty motor over 1 horsepower has no marked service factor and no marked temperature rise. What is the maximum overload device rating as a percentage of nameplate full-load current?

  • a.140 percent
  • b.125 percent
  • c.115 percent
  • d.175 percent

Motors that carry neither a service factor of 1.15 or greater nor a marked temperature rise of 40 degrees C or less are limited to 115 percent of nameplate current, because there is less thermal margin available. The 125 percent value applies to the better-rated motors, 140 percent is the permitted increase when the motor will not start, and 175 percent is a fuse sizing percentage.2023 NEC §430.32(A)(1)

Motors & Equipment

Where must a motor disconnecting means be located relative to the motor?

  • a.Within 25 feet of the motor in all cases
  • b.In sight from the motor location and the driven machinery, unless it is capable of being locked in the open position
  • c.Anywhere on the same floor level as the motor
  • d.In sight from the motor controller only, on the theory that the controller disconnect is always sufficient and that no separate in-sight rule applies to the motor itself

A disconnect must be in sight from the motor and driven machinery so a technician working on the equipment can see that it is open; the alternative is a disconnect elsewhere that is capable of being individually locked in the open position with the locking means remaining in place. In sight means visible and not more than 50 feet away, and a separate rule requires a disconnect in sight from the controller.2023 NEC §430.102(B)

Motors & Equipment

An air conditioning condensing unit nameplate reads minimum circuit ampacity 24.6 and maximum overcurrent protective device 40. What overcurrent device must be installed?

  • a.A 30-ampere device, the next standard size above the minimum circuit ampacity
  • b.A 25-ampere device to match the minimum circuit ampacity
  • c.A 50-ampere device sized at 125 percent of the marked maximum
  • d.A device not exceeding 40 amperes

The marked maximum overcurrent protective device value is a ceiling set by the equipment manufacturer and tested with the unit, so the installed device must not exceed 40 amperes; a smaller device is acceptable only if it will carry the starting current. The minimum circuit ampacity of 24.6 sizes the conductors, not the protective device, and nothing permits multiplying the marked maximum by another factor.2023 NEC §440.4(B)

Motors & Equipment

A hermetic refrigerant motor-compressor has a rated-load current of 20 amperes. What is the maximum branch-circuit short-circuit and ground-fault protective device at the standard 175 percent figure?

  • a.60 amperes
  • b.25 amperes
  • c.45 amperes
  • d.35 amperes

Protection for a motor-compressor is sized at not more than 175 percent of the rated-load current: 20 x 1.75 = 35 A, which is a standard rating. Where that device still will not carry the starting current it may be increased, but never above 225 percent, which here would be 45 amperes. A 25-ampere device is below the calculated value and would nuisance trip on start.2023 NEC §440.22(A)

Motors & Equipment

For that same 20-ampere rated-load compressor supplied alone, what minimum conductor ampacity is required?

  • a.35 amperes
  • b.20 amperes
  • c.25 amperes
  • d.30 amperes

Branch-circuit conductors for a single motor-compressor must have an ampacity of at least 125 percent of the rated-load current or branch-circuit selection current, whichever is greater: 20 x 1.25 = 25 A, which calls for 10 AWG copper. The 35-ampere figure is the 175 percent protective device calculation, and 20 amperes omits the required multiplier entirely.2023 NEC §440.32

Motors & Equipment

A surface-mounted luminaire with a completely enclosed light source is installed in a clothes closet. What is the minimum clearance to the nearest point of the defined storage space?

  • a.12 inches
  • b.6 inches
  • c.3 inches
  • d.18 inches

Surface-mounted luminaires with a completely enclosed light source require 12 inches of clearance from the storage space, while recessed luminaires with an enclosed light source are permitted at 6 inches because the housing is set back into the ceiling or wall. Open incandescent lamps are not permitted in clothes closets at all.2023 NEC §410.16(C)

Motors & Equipment

A recessed luminaire that is NOT identified for insulation contact must maintain what minimum clearance from thermal insulation?

  • a.1 inch
  • b.1/2 inch
  • c.6 inches
  • d.3 inches

A non-IC recessed luminaire must be spaced at least 3 inches from thermal insulation so heat can dissipate, and insulation must not be installed above it in a way that traps heat. The 1/2-inch dimension is the required clearance from combustible materials other than the mounting surface, which is a different measurement.2023 NEC §410.116

Motors & Equipment

A generator nameplate current rating is 200 amperes. What minimum conductor ampacity is required from the generator terminals to the first overcurrent device?

  • a.230 amperes
  • b.200 amperes
  • c.250 amperes
  • d.160 amperes

Conductors from generator terminals to the first distribution device must have an ampacity of at least 115 percent of the nameplate current rating: 200 x 1.15 = 230 A, which corresponds to 4/0 copper at 75 degrees C. The 200-ampere answer omits the factor, 250 amperes uses 125 percent, and 160 amperes derates rather than uprates.2023 NEC §445.13(A)

Motors & Equipment

A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?

  • a.12.5 amperes
  • b.15.6 amperes
  • c.10 amperes
  • d.20 amperes

The maximum circuit current is 125 percent of the rated short-circuit current, or 10 x 1.25 = 12.5 A, and the conductor must then be sized at 125 percent of that value without adjustment factors: 12.5 x 1.25 = 15.6 A. The 12.5-ampere answer stops after only the first multiplier, and 10 amperes ignores both.2023 NEC §690.8

Motors & Equipment

A motor with a service factor of 1.16 will not start because the overload device trips, even though it is sized at 125 percent of nameplate current. To what maximum percentage may the overload device be increased?

  • a.140 percent
  • b.130 percent
  • c.150 percent
  • d.175 percent

Where the overload device selected at the basic percentage is not sufficient to start the motor or carry the load, motors with a service factor of 1.15 or greater or a marked temperature rise of 40 degrees C or less may be increased to 140 percent of nameplate current. The 130 percent ceiling applies to all other motors, and 175 percent is a fuse percentage for short-circuit protection.2023 NEC §430.32(C)

Motors & Equipment

What is the maximum non-time-delay fuse permitted for branch-circuit short-circuit and ground-fault protection of a 34-ampere three-phase squirrel-cage motor, using the next standard size allowance?

  • a.110 amperes
  • b.100 amperes
  • c.90 amperes
  • d.125 amperes

Non-time-delay fuses are permitted at 300 percent of full-load current: 34 x 3.00 = 102 A, which is not a standard rating, so the next standard size of 110 amperes may be used. The 90-ampere answer belongs to the inverse-time breaker at 250 percent, and 125 amperes skips a standard size.2023 NEC Table 430.52(C)(1)

Motors & Equipment

A 20-horsepower, 208-volt three-phase motor has a table full-load current of 59.4 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?

  • a.6 AWG
  • b.4 AWG
  • c.3 AWG
  • d.8 AWG

The conductor must carry 59.4 x 1.25 = 74.25 A. In the 75 degrees C column, 6 AWG copper is 65 A and falls short, while 4 AWG copper at 85 A is adequate. Choosing 3 AWG is oversized for the minimum, and 8 AWG at 50 A is well below the requirement.2023 NEC §430.22

Motors & Equipment

How many running overload protective devices are required for a three-phase alternating-current motor?

  • a.One
  • b.Two
  • c.Three, one in each phase
  • d.Four

Table 430.37 requires a three-phase motor to have an individual overload device in each of the three ungrounded conductors, so that a single-phasing condition, which overloads the remaining windings, is detected. One or two devices could miss an overload on an unprotected phase.2023 NEC §430.37

Motors & Equipment

A 25-kVA, single-phase transformer has a 480-volt primary and is protected by primary overcurrent protection only, sized at 125 percent. With a primary full-load current of 9 amperes or more, what is the maximum standard primary overcurrent device rating?

  • a.60 amperes
  • b.50 amperes
  • c.65 amperes
  • d.70 amperes

Primary current is 25,000 / 480 = 52.1 amperes, and 52.1 x 1.25 = 65.1 amperes. Because that value is not a standard rating, the next higher standard size of 70 amperes is permitted. 65 amperes is not a standard overcurrent device rating, and 60 amperes would be below the calculated value.2023 NEC §450.3(B)

Motors & Equipment

On a feeder supplying several motors, 125 percent is applied to which motor's full-load current?

  • a.The highest-rated motor, meaning the one with the largest full-load current
  • b.The smallest motor
  • c.Every motor on the feeder
  • d.The motor with the highest horsepower nameplate regardless of current

Feeder conductors are sized at 125 percent of the largest motor full-load current plus the sum of the full-load currents of the other motors, and the largest motor is the one with the highest rated full-load current per 430.17. Applying 125 percent to every motor over-sizes the feeder.2023 NEC §430.24

Motors & Equipment

An outlet box used as the sole support of a ceiling-suspended paddle fan must meet what requirement?

  • a.Any 4-inch box rated for 50 pounds is acceptable
  • b.It must be listed and marked for the purpose of supporting a fan, and fans over 70 pounds require additional independent support
  • c.It must be a nonmetallic box only
  • d.No special outlet box is required as long as two long wood screws are driven through the box and directly into the structural framing member above

Outlet boxes are not permitted as the sole support of a ceiling fan unless they are listed and marked for that purpose, and a fan exceeding 70 pounds must be supported independently of the box. A standard lighting outlet box is not rated for the dynamic load of a rotating fan.2023 NEC §314.27(C)

Motors & Equipment

Within what zone measured from the rim of a bathtub or the threshold of a shower stall are hanging luminaires and ceiling-suspended paddle fans generally prohibited?

  • a.2 feet horizontally and 6 feet vertically
  • b.5 feet horizontally and 10 feet vertically
  • c.3 feet horizontally and 8 feet vertically
  • d.6 feet horizontally and 8 feet vertically

Cord-connected luminaires, hanging luminaires, track lighting, pendants and ceiling fans are not permitted within a zone of 3 feet horizontally and 8 feet vertically from the top of the bathtub rim or shower threshold, keeping them out of reach of a wet person. Fixed luminaires outside that zone are acceptable.2023 NEC §410.10(D)

Motors & Equipment

A cord-and-plug-connected room air conditioner is the only load on its branch circuit. Its total rating must not exceed what percentage of the branch-circuit rating?

  • a.100 percent
  • b.80 percent
  • c.50 percent
  • d.125 percent

Where the room air conditioner is the only load on the circuit, its marked rating may not exceed 80 percent of the branch-circuit rating. If lighting units or other appliances are also supplied by the circuit, that ceiling drops to 50 percent.2023 NEC §440.62(B)

Motors & Equipment

An indoor dry-type transformer rated more than 112.5 kVA must generally be installed in what manner?

  • a.Installed no less than six inches away from any combustible material, or otherwise provided with a listed thermal barrier, with no requirement for a fire-resistant transformer room no matter how large the unit is
  • b.On a raised concrete pad only
  • c.Within sight of the main service
  • d.In a transformer room of fire-resistant construction, unless it has Class 155 or higher insulation and is separated from combustibles by a barrier or by adequate distance

Dry-type transformers over 112.5 kVA installed indoors must be in a transformer room of fire-resistant construction, with exceptions for units having Class 155 or higher insulation that are either completely enclosed or separated from combustible material by a fire-resistant barrier or by clearance. Units of 112.5 kVA or less instead follow the 12-inch clearance rule.2023 NEC §450.21(B)

Motors & Equipment

A 20-horsepower, 460-volt, three-phase squirrel-cage motor has a table full-load current of 27 amperes. Using 75 degrees C copper terminations, what is the minimum branch-circuit conductor size?

  • a.8 AWG
  • b.12 AWG
  • c.6 AWG
  • d.10 AWG

Single-motor branch-circuit conductors must carry at least 125 percent of the table full-load current: 27 x 1.25 = 33.75 A. In the 75 degrees C column 12 AWG (25 A) fails and 10 AWG (35 A) qualifies. See NEC 430.22, Table 430.250 and Table 310.16.

Motors & Equipment

That 20-horsepower motor has a nameplate full-load current of 26 amperes and a marked service factor of 1.15. What is the maximum separate overload device rating?

  • a.33.75 amperes
  • b.29.9 amperes
  • c.32.5 amperes
  • d.26 amperes

Overload protection is based on nameplate current, and a service factor of 1.15 or greater permits 125 percent: 26 x 1.25 = 32.5 A. The 115 percent factor (29.9 A) applies only to lower-rated motors. See NEC 430.32(A)(1).

Motors & Equipment

For that 27-ampere three-phase motor, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection, using the next standard size allowance?

  • a.90 amperes
  • b.70 amperes
  • c.60 amperes
  • d.80 amperes

An inverse-time breaker is permitted at 250 percent of full-load current: 27 x 2.50 = 67.5 A, which is not standard, so the next standard size of 70 A may be used. See Table 430.52(C)(1) and 430.52(C)(1) Exception 1.

Motors & Equipment

For the same 27-ampere motor, what is the maximum dual-element time-delay fuse at the standard 175 percent, using the next standard size allowance?

  • a.40 amperes
  • b.50 amperes
  • c.60 amperes
  • d.45 amperes

Dual-element time-delay fuses are permitted at 175 percent: 27 x 1.75 = 47.25 A, and the next standard size is 50 A. See Table 430.52(C)(1).

Motors & Equipment

For the same 27-ampere motor, what is the maximum non-time-delay fuse at the standard 300 percent, using the next standard size allowance?

  • a.110 amperes
  • b.80 amperes
  • c.90 amperes
  • d.100 amperes

Non-time-delay fuses are permitted at 300 percent: 27 x 3.00 = 81 A, and the next standard size is 90 A. See Table 430.52(C)(1).

Motors & Equipment

A 25-horsepower, 208-volt, three-phase squirrel-cage motor has a table full-load current of 74.8 amperes. Using 75 degrees C copper terminations, what is the minimum branch-circuit conductor size?

  • a.6 AWG
  • b.4 AWG
  • c.2 AWG
  • d.3 AWG

The conductor must carry 74.8 x 1.25 = 93.5 A. In the 75 degrees C column 4 AWG (85 A) fails and 3 AWG (100 A) qualifies. See NEC 430.22, Table 430.250 and Table 310.16.

Motors & Equipment

For that 74.8-ampere motor, what is the maximum inverse-time circuit breaker at 250 percent, using the next standard size allowance?

  • a.150 amperes
  • b.200 amperes
  • c.225 amperes
  • d.175 amperes

74.8 x 2.50 = 187 A, which is not standard, so the next standard size of 200 A may be used. See Table 430.52(C)(1).

Motors & Equipment

A feeder supplies a 25-horsepower motor (34 amperes) and a 15-horsepower motor (21 amperes), both 460 volts three-phase. What minimum conductor ampacity is required?

  • a.68.75 amperes
  • b.48.75 amperes
  • c.63.5 amperes
  • d.55 amperes

Feeder conductors carry 125 percent of the largest motor plus the other full-load currents: (34 x 1.25) + 21 = 42.5 + 21 = 63.5 A. See NEC 430.24.

Motors & Equipment

For that two-motor feeder, if the largest branch-circuit protective device is 90 amperes, what is the maximum feeder overcurrent device rating?

  • a.100 amperes
  • b.111 amperes
  • c.125 amperes
  • d.110 amperes

The feeder device may not exceed the largest branch device plus the other motors' full-load currents: 90 + 21 = 111 A. Since 111 is not standard and this is a maximum, the next lower standard size of 110 A is used. See NEC 430.62(A).

Motors & Equipment

An air-conditioning condensing unit is marked minimum circuit ampacity 28.4 amperes. Using 75 degrees C copper, what is the minimum branch-circuit conductor size?

  • a.8 AWG copper
  • b.14 AWG copper
  • c.10 AWG copper
  • d.12 AWG copper

The minimum circuit ampacity sizes the conductors: 28.4 A calls for 10 AWG copper (35 A at 75 degrees C). See NEC 440.32 and 440.4(B).

Motors & Equipment

A hermetic refrigerant motor-compressor has a rated-load current of 22 amperes. What is the maximum branch-circuit short-circuit and ground-fault protective device at the standard 175 percent?

  • a.45 amperes
  • b.50 amperes
  • c.40 amperes
  • d.35 amperes

Protection is sized at not more than 175 percent of the rated-load current: 22 x 1.75 = 38.5 A, and the next standard size is 40 A. See NEC 440.22(A).

Motors & Equipment

For that same 22-ampere rated-load compressor supplied alone, what minimum conductor ampacity is required?

  • a.30 amperes
  • b.22 amperes
  • c.38.5 amperes
  • d.27.5 amperes

Branch-circuit conductors for a single motor-compressor must be at least 125 percent of the rated-load or branch-circuit selection current: 22 x 1.25 = 27.5 A, which calls for 10 AWG copper. See NEC 440.32.

Motors & Equipment

A recessed luminaire with a completely enclosed light source is installed in a clothes closet. What is the minimum clearance from the nearest point of the defined storage space?

  • a.6 inches
  • b.3 inches
  • c.18 inches
  • d.12 inches

A recessed luminaire with a completely enclosed light source may be as close as 6 inches to the storage space, while a surface-mounted enclosed luminaire requires 12 inches. See NEC 410.16(C)(2).

Motors & Equipment

A recessed luminaire not identified for insulation contact must be spaced at least what distance from combustible materials, other than at points of support?

  • a.1 inch
  • b.1/2 inch
  • c.3 inches
  • d.6 inches

A non-IC recessed luminaire must be at least 1/2 inch from combustible materials, other than at the points of support, and 3 inches from thermal insulation. See NEC 410.116(A)(1).

Motors & Equipment

A generator nameplate current rating is 150 amperes. What minimum conductor size is required from the generator terminals to the first overcurrent device, using 75 degrees C copper?

  • a.3/0 AWG
  • b.2/0 AWG
  • c.1 AWG
  • d.1/0 AWG

Conductors from the generator terminals to the first device must be at least 115 percent of the nameplate current: 150 x 1.15 = 172.5 A. In the 75 degrees C column 1/0 (150 A) fails and 2/0 (175 A) qualifies. See NEC 445.13(A).

Motors & Equipment

A photovoltaic source circuit uses modules with a rated short-circuit current of 8 amperes. What minimum conductor ampacity is required before any adjustment factors?

  • a.15.6 amperes
  • b.12.5 amperes
  • c.8 amperes
  • d.10 amperes

The maximum circuit current is 125 percent of the rated short-circuit current: 8 x 1.25 = 10 A, and the conductor is then sized at 125 percent of that value: 10 x 1.25 = 12.5 A. See NEC 690.8(A) and (B).

Motors & Equipment

A continuous-duty motor with no marked service factor and no marked temperature rise will not start because the overload device selected at the basic percentage keeps tripping. To what maximum percentage of nameplate current may the overload device be increased?

  • a.125 percent
  • b.150 percent
  • c.130 percent
  • d.140 percent

Motors that do not have a service factor of 1.15 or greater or a marked temperature rise of 40 degrees C or less may be increased only to 130 percent, while better-rated motors may go to 140 percent. See NEC 430.32(C).

Motors & Equipment

How many running overload protective devices are required for a single-phase, two-wire alternating-current motor?

  • a.One
  • b.Three
  • c.Four
  • d.Two

Table 430.37 requires one overload device in one ungrounded conductor for a single-phase, two-wire motor, whereas a three-phase motor requires one in each of the three phases. See NEC Table 430.37.

Motors & Equipment

A 15-kVA, single-phase transformer has a 480-volt primary and is protected by primary overcurrent protection only at 125 percent. What is the maximum standard primary overcurrent device rating?

  • a.35 amperes
  • b.45 amperes
  • c.40 amperes
  • d.50 amperes

Primary full-load current = 15,000 / 480 = 31.25 A, and 31.25 x 1.25 = 39.06 A. The next standard rating is 40 A. See NEC 450.3(B).

Motors & Equipment

What is the maximum weight of a ceiling-suspended paddle fan that may be supported solely by a listed fan-rated outlet box without additional independent support?

  • a.70 pounds
  • b.50 pounds
  • c.90 pounds
  • d.35 pounds

A fan-listed outlet box may support a fan up to 70 pounds; a fan exceeding 70 pounds must be supported independently of the box. See NEC 314.27(C).

Motors & Equipment

A cord-and-plug-connected room air conditioner shares its branch circuit with lighting outlets. Its total marked rating must not exceed what percentage of the branch-circuit rating?

  • a.100 percent
  • b.80 percent
  • c.50 percent
  • d.125 percent

Where lighting units or other appliances are also supplied, a room air conditioner may not exceed 50 percent of the branch-circuit rating; if it is the only load, the limit is 80 percent. See NEC 440.62(B) and (C).

Motors & Equipment

Capacitor circuit conductors must have an ampacity of at least what percentage of the rated current of the capacitor?

  • a.135 percent
  • b.150 percent
  • c.125 percent
  • d.115 percent

Conductors supplying a capacitor must be sized at not less than 135 percent of the rated current of the capacitor. See NEC 460.8(A).

Motors & Equipment

As defined in Article 100, what does 'in sight from' mean in terms of distance?

  • a.Anywhere on the same floor level
  • b.Visible and not more than 50 feet away
  • c.Within 75 feet whether visible or not
  • d.Visible and not more than 25 feet away

'In sight from' means the equipment is visible and not more than 50 feet distant from the other equipment. See NEC Article 100.

Motors & Equipment

A 40-horsepower, 460-volt, three-phase motor has a table full-load current of 52 amperes. What minimum ampere rating must the disconnecting means have?

  • a.46 amperes
  • b.65 amperes
  • c.52 amperes
  • d.59.8 amperes

The disconnecting means must be at least 115 percent of the full-load current: 52 x 1.15 = 59.8 A, so a 60-ampere or larger switch would be selected. See NEC 430.110(A).

Motors & Equipment

A 5-horsepower, 460-volt, three-phase motor has a table full-load current of 7.6 amperes. Using 75 degrees C copper, what is the minimum branch-circuit conductor size?

  • a.16 AWG
  • b.14 AWG
  • c.12 AWG
  • d.10 AWG

The conductor must carry 7.6 x 1.25 = 9.5 A. 14 AWG copper (20 A at 75 degrees C) is adequate; motor branch-circuit conductors are sized under Article 430 and are not restricted by the small-conductor rule of 240.4(D). See NEC 430.22.

Motors & Equipment

A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C. What percentage of nameplate full-load current sets the maximum overload device?

  • a.140 percent
  • b.115 percent
  • c.125 percent
  • d.130 percent

A motor with a marked temperature rise not over 40 degrees C, like one with a service factor of 1.15 or greater, is permitted overload protection at 125 percent of nameplate current. See NEC 430.32(A)(1).

Motors & Equipment

A feeder supplies a 30-horsepower motor (40 amperes), a 20-horsepower motor (27 amperes) and a 10-horsepower motor (14 amperes), all 460 volts three-phase. What minimum conductor ampacity is required?

  • a.91 amperes
  • b.101.25 amperes
  • c.81 amperes
  • d.95 amperes

Feeder ampacity = 125 percent of the largest motor plus the sum of the others: (40 x 1.25) + 27 + 14 = 50 + 41 = 91 A. See NEC 430.24.

这门考试有多难?

熟练/普通电工认证由各州主办、以 NEC 为依据,因此格式因州而异。例如加州的普通电工考试为 100 题,4.5 小时,70% 及格,各项费用合计约 175 美元。电工年薪中位数约 62,350 美元(BLS,2024 年 5 月)。

推荐学习时间
多数人 60-120 小时——NEC 查规范、负载计算与导线/导管选型内容偏重。
首次通过率
51.22% 首次应考(n = 4,150);39.75% 重考(n = 4,150) —— California DIR Electrician Certification Unit,2023。这是加州 General Electrician 考试,也是少数真正公布首考/重考分列数据的技工类考试之一 —— n 为两类考生合计的年度考试次数。执照按州发放,因此这只是一个州的数字:德州 TDLR 公布其 Journeyman 考试 FY 2025 为 27.52%(n = 5,050),但未说明统计的是哪些考次。来源: California DIR/DLSE Electrician Certification Unit — California Electrical Examinations Statistical Overview 2023 (PDF) · Texas TDLR — Electrician Exam Statistics, Fiscal Year 2025
重点学习方向
安装(Installation)在加州考试中占比最大,达 66%——依 NEC 的布线方式、接线盒、导线、服务与设备。

费用与薪资为近似值,会随时间变动。上方的通过率引自旁边链接的来源,并限于该来源覆盖的期间——凡是我们尚未核实来源的,都会直接说明并且不给数字。

反馈