Branch Circuits & Feeders第 26 / 120 题
What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?
a.195 amperes
b.205 amperes
c.260 amperes
d.230 amperes
解析
Table 310.16 lists 4/0 copper at 230 amperes in the 75 degrees C column. The 260-ampere figure is the 90 degrees C value and may be used only as a derating base, 195 amperes is the 60 degrees C value, and 205 amperes belongs to 3/0 copper at 90 degrees C rather than 4/0.
法律依据: 2023 NEC Table 310.16免费刷完整 120 道题库 — 无需注册。