Branch Circuits & Feeders第 27 / 120 题
Twelve current-carrying 12 AWG THHN copper conductors run in one raceway through a 38 degrees C ambient. What is the adjusted ampacity of each conductor?
a.15 amperes
b.13.65 amperes
c.12 amperes
d.10.9 amperes
解析
Start at the 90 degrees C ampacity of 30 A, apply the 36 to 40 degrees C correction factor of 0.91, then the 50 percent adjustment for 10 through 20 conductors: 30 x 0.91 x 0.50 = 13.65 A. Answers of 15 A and 12 A apply only one of the two factors, and 10.9 A uses the 45 percent bracket that begins at 21 conductors.
法律依据: 2023 NEC §310.15免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A 200-ampere feeder uses THHN copper conductors, but the equipment terminations are rated 75 degrees C. What is the minimum conductor size?
- Using the dwelling service and feeder conductor table, what is the minimum copper conductor size for a 200-ampere single-phase dwelling service?
- What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?
- A 5,000-watt, 240-volt single-phase electric heater operates continuously. What is the minimum standard branch-circuit overcurrent device rating?
- What is the line current of a balanced 45 kVA, three-phase, 208-volt load?
- On a 20-ampere branch circuit that supplies both lighting outlets and cord-and-plug-connected equipment not fastened in place, what is the maximum load the cord-and-plug equipment may impose?