Services, Grounding & Bonding第 37 / 120 题
What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?
a.4 AWG
b.3 AWG
c.2 AWG
d.1 AWG
解析
Table 250.122 lists 3 AWG copper at 400 amperes. 4 AWG is the 300-ampere value, 2 AWG the 500-ampere value and 1 AWG the 600-ampere value, so all three are one row away from the correct entry.
法律依据: 2023 NEC Table 250.122免费刷完整 120 道题库 — 无需注册。