Services, Grounding & Bonding第 40 / 120 题
A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?
a.250 kcmil
b.3/0 AWG
c.4/0 AWG
d.2/0 AWG
解析
Where the ungrounded service conductors exceed 1,100 kcmil of copper, the main bonding jumper must be at least 12.5 percent of that area: 2 x 750 = 1,500 kcmil, and 1,500 x 0.125 = 187.5 kcmil. The smallest standard conductor with at least that area is 4/0 AWG at 211.6 kcmil; 3/0 at 167.8 kcmil falls short and 250 kcmil is larger than the calculated minimum.
法律依据: 2023 NEC §250.28(D)(2)免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?
- A 100-ampere feeder originally sized with 3 AWG copper (52,620 circular mils) is upsized to 1/0 AWG copper (105,600 circular mils) for voltage drop. What is the minimum equipment grounding conductor?
- A service is supplied by a single set of 500 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?
- Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
- Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
- A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?