Wiring Methods & Materials第 72 / 120 题
At what maximum interval must Type AC cable be supported?
a.Every 6 feet
b.Every 4 and 1/2 feet
c.Every 10 feet
d.Every 3 feet
解析
Type AC armored cable is supported at intervals not exceeding 4 and 1/2 feet and secured within 12 inches of each termination. The 6-foot figure is for Type MC cable and 10 feet is for EMT, so mixing the cable types is the usual source of error here.
法律依据: 2023 NEC §320.30免费刷完整 120 道题库 — 无需注册。