Motors & Equipment第 87 / 120 题
For the same 34-ampere motor, what is the maximum dual-element time-delay fuse permitted at the standard percentage?
a.60 amperes
b.70 amperes
c.50 amperes
d.90 amperes
解析
Dual-element time-delay fuses are permitted at 175 percent of full-load current: 34 x 1.75 = 59.5 A, and because that is not a standard rating the next standard size of 60 amperes is used. The 90-ampere answer belongs to the inverse-time breaker at 250 percent, and 50 amperes falls below the calculated value.
法律依据: 2023 NEC Table 430.52(C)(1)免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A 25-horsepower, 460-volt, three-phase squirrel-cage motor has a table full-load current of 34 amperes. Using 75 degrees C terminations and copper, what is the minimum branch-circuit conductor size?
- That same motor has a nameplate full-load current of 32 amperes and a marked service factor of 1.15. What is the maximum separate overload device rating?
- For that 34-ampere three-phase squirrel-cage motor, what is the maximum inverse-time circuit breaker permitted for branch-circuit short-circuit and ground-fault protection, using the next standard size allowance?
- A 5-horsepower, 230-volt single-phase motor has a table full-load current of 28 amperes. What is the minimum copper branch-circuit conductor at 75 degrees C terminations?
- A 30-horsepower, 460-volt three-phase motor has a table full-load current of 40 amperes. What is the minimum ampere rating of the disconnecting means?
- A feeder supplies a 25-horsepower motor (34 amperes) and a 10-horsepower motor (14 amperes), both 460 volts three phase. What minimum conductor ampacity is required?