Fixtures & Water Heaters第 70 / 120 题
The same gas water heater is installed in that garage on a concrete slab. What is the minimum height that the source of ignition must be elevated above the garage floor?
a.18 inches
b.12 inches
c.24 inches
d.6 inches
解析
Ignition sources in a garage must be at least 18 inches above the floor because gasoline vapors are heavier than air and pool at floor level. 12 inches and 6 inches leave the burner inside the vapor layer. 24 inches is higher than required and is not the code figure, although a taller platform would still comply.
免费刷完整 120 道题库 — 无需注册。
同考点相关题目
- A temperature and pressure relief valve has a 3/4 inch outlet. Which discharge piping arrangement is acceptable?
- A 50 gallon water heater is installed in the attic above a finished ceiling. A drain pan is required. What is the minimum size of the pan drain line?
- A gas fired water heater is installed in a residential garage in a seismic zone. It must be strapped in two places. Where must the lower strap be located relative to the heater's controls?
- A 120,000 Btu/h gas water heater draws all of its combustion air directly from outdoors through two vertical ducts. Using the 1 square inch per 4,000 Btu/h rule for vertical ducts, what is the required free area of each opening?
- A 100,000 Btu/h water heater is placed in a closet and will take combustion air from inside the building only. Using the rule of thumb of 50 cubic feet of room volume per 1,000 Btu/h, what minimum volume of communicating space is needed?
- Where an enclosure takes combustion air from an adjacent room through two permanent openings, where must those openings be located?