Systems & Code第 34 / 110 题
A commercial kitchen installs a grease interceptor rated for a flow of 35 gpm. Using the common rule that grease capacity in pounds is about twice the gpm rating, what nominal grease retention does this unit provide, and what is its purpose?
a.35 lb, to trap sand
b.70 lb, to intercept fats, oils and grease
c.150 lb, to neutralize acid
d.300 lb, to settle solids
解析
A hydromechanical grease interceptor rated at 35 gpm provides roughly 70 lb of grease retention and its purpose is to intercept fats, oils, and grease before they enter and clog the building drain and public sewer. Interceptors are sized by fixture flow and required retention. Sand interceptors and acid neutralizers serve entirely different wastes.
法律依据: IPC §1003.4免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A wet-vented bathroom group discharges 5 DFU to a wet vent section. Wet vent capacity limits are 1-1/2 in = 1 DFU, 2 in = 4 DFU, and 3 in = 6 DFU. What is the minimum wet vent size?
- A circuit vent serves a battery of floor-mounted fixtures on a horizontal branch. What is the maximum number of fixtures a single circuit vent may serve, and where is the vent taken off?
- A building drain serving fixtures below the elevation of the public sewer manhole must be protected against sewer backflow. Which device is required on that low-level drainage?
- A basement floor drain sits 3 ft below the elevation of the upstream sewer manhole cover. During a main surcharge, how much backpressure head could push up through that drain if unprotected, using 0.433 psi per foot?
- A hot-water recirculation loop loses 4,000 BTU/hr to the piping. The pump must circulate enough water so it cools only 20 F while replacing that loss. Using Q (gpm) = BTU/hr / (500 x delta-T), what recirculation flow is required?
- A temperature-and-pressure (T and P) relief valve on a water heater is rated to open at 210 F and 150 psi. What is the required disposition of its discharge pipe?