A hot-water recirculation loop loses 4,000 BTU/hr to the piping. The pump must circulate enough water so it cools only 20 F while replacing that loss. Using Q (gpm) = BTU/hr / (500 x delta-T), what recirculation flow is required?
a.0.4 gpm
b.0.2 gpm
c.0.8 gpm
d.2.0 gpm
解析
Q = 4,000 / (500 x 20) = 4,000 / 10,000 = 0.4 gpm. The 500 factor is the heat capacity of water in BTU per hour per gpm per degree F. A low recirculation flow is enough to offset standby losses and keep hot water instantly available without eroding the piping.
法律依据: UPC §608.0免费刷完整 110 道题库 — 无需注册。
同考点相关题目
- A commercial kitchen installs a grease interceptor rated for a flow of 35 gpm. Using the common rule that grease capacity in pounds is about twice the gpm rating, what nominal grease retention does this unit provide, and what is its purpose?
- A building drain serving fixtures below the elevation of the public sewer manhole must be protected against sewer backflow. Which device is required on that low-level drainage?
- A basement floor drain sits 3 ft below the elevation of the upstream sewer manhole cover. During a main surcharge, how much backpressure head could push up through that drain if unprotected, using 0.433 psi per foot?
- A temperature-and-pressure (T and P) relief valve on a water heater is rated to open at 210 F and 150 psi. What is the required disposition of its discharge pipe?
- A closed water-supply system (with a backflow preventer or check valve at the meter) has a water heater but no expansion control. As the water heats and expands, what device is required to prevent pressure buildup?
- A reduced-pressure principle (RP) backflow assembly is installed on a service subject to a health hazard. How must it be installed with respect to the ground and drainage?