A concrete-encased electrode ('Ufer' ground) used as a grounding electrode must include at least how many feet of bare steel rebar or copper conductor encased in the footing?

a.10 feet
b.30 feet
c.50 feet
d.20 feet

Explanation

A concrete-encased electrode must consist of at least 20 feet of 1/2-inch (or larger) bare rebar or 4 AWG copper encased in at least 2 inches of concrete near the bottom of a foundation. The moist concrete-to-earth contact makes it a very effective electrode. 10 feet is insufficient; 30 and 50 feet exceed the minimum.

Law Reference: 2025 CA Electrical Code, Art. 250.52