Framing & StructuralQuestion 320 of 700
When rafters frame to a non-structural ridge board (not a ridge beam), what is the minimum requirement for that ridge board's depth?
a.Not less than the cut end (plumb-cut depth) of the rafter
b.Exactly 2 inches regardless of rafter size
c.Twice the rafter depth
d.Half the rafter depth
Explanation
A ridge board must be at least as deep as the cut (plumb) end of the rafters bearing against it so the full rafter end seats against the board. A fixed 2 inches, twice, or half the rafter depth would either under- or over-size the board relative to the rafter end it must fully support.
Law Reference: 2025 CA Residential Code §R802.3Practice all 700 questions free — no signup required.
Related questions on this topic
- In a braced wall line, what does the term 'braced wall panel' refer to?
- In conventional roof framing, where should rafter ties (which resist the outward thrust of rafters) generally be located?
- What is the practical difference between a collar tie and a rafter tie in a gable roof?
- Why does a structural RIDGE BEAM allow a roof to be built without rafter ties, whereas a simple ridge BOARD does not?
- Collar ties used to resist wind uplift should be spaced no farther apart than what, measured along the ridge?
- CALCULATION: A common rafter runs horizontally 12 feet from the wall to the ridge and rises 9 feet. Ignoring overhang and cuts, what is the approximate rafter line length?