Branch Circuits & WiringQuestion 120 of 521

What is the minimum number of 20-ampere small-appliance branch circuits required to serve the receptacle outlets in a dwelling kitchen, pantry, breakfast room, and dining room?

a.2
b.1
c.3
d.4

Explanation

Section 210.11(C)(1) requires at least two 20-A small-appliance branch circuits for these areas. These circuits serve countertop and receptacle outlets and cannot supply lighting. One circuit is insufficient; three or four exceed the code minimum.

Law Reference: 2023 NEC §210.11(C)(1)