Branch Circuits & WiringQuestion 147 of 521
Where cables or raceways are run parallel to framing members, the wiring must be kept at least what distance from the nearest edge of a wood stud where nails or screws are likely, unless protected by a steel plate?
a.3/4 in
b.1 in
c.1-1/8 in
d.1-1/4 in
Explanation
Section 300.4(D) requires cables and raceways run parallel to framing to be at least 1-1/4 in from the nearest edge where nails or screws are likely; otherwise a 1/16-in steel plate is required. The smaller distances of 3/4, 1, and 1-1/8 in do not provide the required setback.
Law Reference: 2023 NEC §300.4(D)Practice all 521 questions free — no signup required.
Related questions on this topic
- Expansion fittings for rigid PVC conduit must be provided to compensate for thermal expansion and contraction where the length change is expected to be at least how much?
- Under Table 300.5, what is the minimum burial depth for a direct-buried rigid metal conduit (RMC) installed under a residential driveway of a one-family dwelling?
- Per Table 300.5, what is the minimum cover for direct-buried UF cable (without other protection) not under a driveway, in a residential branch circuit application?
- Branch-circuit conductors must have an ampacity not less than the maximum load to be served and, before the application of adjustment or correction factors, not less than what portion of the continuous load?
- A single receptacle installed on an individual branch circuit must have an ampere rating not less than what value relative to the branch circuit?
- On a 20-ampere branch circuit supplying two or more receptacles, a single cord-and-plug-connected utilization equipment item must not have a rating exceeding what value?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review