Branch Circuits & WiringQuestion 195 of 521

Per Annex C, Table C.1, what is the maximum number of 12 AWG THHN conductors permitted in 3/4" EMT?

a.9
b.22
c.16
d.12

Explanation

Table C.1 lists 16 for 12 AWG THHN in 3/4" EMT. 22 is the count for 14 AWG in 3/4" EMT, and 9 is the count for 12 AWG in the smaller 1/2" EMT.

Law Reference: 2023 NEC Annex C, Table C.1