Branch Circuits & WiringQuestion 199 of 521

Given a 40% usable fill area of 0.213 in² (3/4" EMT) and a 12 AWG THHN cross-sectional area of 0.0133 in² (Table 5), how many 12 AWG THHN conductors fit?

a.9
b.12
c.16
d.22

Explanation

0.213 ÷ 0.0133 = 16.0, so 16 conductors fit — matching Annex C. 9 corresponds to 1/2" EMT, 22 is the 14 AWG count for 3/4", and 12 is not correct here.

Law Reference: 2023 NEC Chapter 9, Table 4